Mitsubishi Electric MXZ-SM36NAM2 Technical & Service Manual page 141

Split-type, heat pump air conditioners, outdoor unit, hfc utilized r410a
Table of Contents

Advertisement

Method of Combined Branching of Lines and
Headers
Connection Examples
(Connecting to 5 Indoor Units)
Total Piping Length
Permissible
Farthest Piping Length
Length
Farthest Piping Length After First Branch
Permissible High/
High/Low Difference
Low Difference
in Indoor/Outdoor Section
High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d,e)
(3) Section From Branch to
Branch (B,C)
Select the size from the table to the right.
Additional refrigerant charge
OCH810A
A
A
B
A+B+C+a+b+c+d+e
(L)
A+B+b
492 ft [150 m]
( )
B+b
98 ft [30 m]
The outdoor unit is upper: 164ft [50m] or less
(H)
The outdoor unit is lower: 131ft [40m] or less (98ft [30,] or less if PKFY-P04/06/08/12NLMU,
PFFY-P06/08/12NEMU, and PFFY-P06/08/12NRMU are included.)
(h)
49 ft [15 m]
Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Branch Joint
CMY-Y62-G-E
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch
(Outdoor Unit Piping Diameter)
Model
Each
Section of
Piping
MXZ-SM36/42/48
(3) Refrigerant Piping Diameter In Section
From Branch to Branch
Liquid Line (inch [mm]) Gas Line (inch [mm])
3/8 [ø9.52]
Refer to the same section in the previous page.
141
Note: Pipe re-branching after the header branching
is not possible.
C
c
d
3
4
B
D
D
L
b
a
2
C
D
1
984 ft [300 m]
Branch Header (4 branches)
CMY-Y64-G-E
Piping Diameter (inch [mm])
Liquid Line
3/8 [ø9.52]
Gas Line
5/8 [ø15.88]
5/8 [ø15.88]
E
F
e
A
Outdoor unit
5
B
First branching (branching
D
joint)
C
Branching joint
D
Indoor unit
E
Branching header
F
Blind caps
D
Branch Header (8 branches)
CMY-Y68-G-E
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit
(Indoor Unit Piping Diameter)
Model number
Piping Diameter(inch [mm])
Liquid Line
1/4 [ø6.35 ]
18 or lower
Gas Line
1/2 [ø12.7]
Liquid Line
3/8 [ø9.52]
24 to 54
Gas Line
5/8 [ø15.88]