Accessories; Optional Parts; Installation Work; Selecting An Installation Location - Fujitsu AirStage AS A004GTEH Series Installation Manual

Hide thumbs Also See for AirStage AS A004GTEH Series:
Table of Contents

Advertisement

2.3. Accessories

For installation purposes, be sure to use the parts supplied by the manufacturer or other
prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit falling,
water leakage, electric shock, or fire.
• The following installation parts are furnished. Use them as required.
• Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Name and Shape
Q'ty
Operating
Manual
Installation
Manual
Operating
Manual
(CD-ROM)
Wall hook bracket
Tapping screw (M4 × 25 mm)
(004/007/
model)
(030/034
model)
Drain hose Insulation
(030/034
model)
Cloth tape
Cable tie
(030/034
model)
Air cleaning filter
(030/034
model)
Air cleaning filter frame
(030/034
model)

2.4. Optional parts

Description
Model
UTY-XWZXZC For output function (Output terminal / CNB01)
UTY-XWZXZB
UTY-XWZXZD
External connect kit
UTY-XWZXZ7
UTY-XWZXZE
Wireless LAN adapter
UTY-TFSXZ*
External power supply
UTZ-GXXA
unit
WARNING
Application
1
(This book)
1
1
For indoor unit installation.
1
For wall hook bracket installation.
009
5
8
For installing drain hose
1
For indoor unit installation.
1
For transmission and remote controller
cable binding.
2
For installation, refer to the "CLEANING
AND CARE" in the operating manual.
2
2
Application
For control input function (Apply voltage
terminal / CNA01)
For control input function (Dry contact termi-
nal / CNA02)
For forced thermostat off function (Apply volt-
age terminal / CNA03)
For forced thermostat off function (Dry con-
tact terminal / CNA04)
For wireless LAN control.
Supply power to the indoor unit PCB when
the indoor unit is turned off to prevent errors.

3. INSTALLATION WORK

Correct initial installation location is important because it is difficult to move unit after it is
installed.

3.1. Selecting an installation location

Decide the mounting position together with the customer as follows.
Select installation locations that can properly support the weight of the indoor unit.
Install the units securely so that they do not topple or fall.
Do not install the indoor unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts, caus-
ing the parts to fail or the unit to leak water.
• Area filled with mineral oil or containing a large amount of splashed oil or steam, such
as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak
water.
• Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to
corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon fibers or
flammable dust, or volatile inflammables such as paint thinner or gasoline. If gas leaks
and settles around the unit, it can cause a fire.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or flammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, power supply cable, transmission cable, and remote controller
cable at least 1 m away from a television or radio receivers. The purpose of this is to
prevent TV reception interference or radio noise. (Even if they are installed more than 1
m apart, you could still receive noise under some signal conditions.)
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
Take precautions to prevent the unit from falling.
(1) Install the indoor unit on a place having a sufficient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(5) Install the unit where the connection pipe can be easily installed.
(6) Install the unit where the drain pipe can be easily installed.
(7) Install the unit where noise and vibrations are not amplified.
(8) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the filter can be removed.
(9) Do not install the unit where it will be exposed to direct sunlight.
Detection range of the human sensor (030/034 model only)
Do not hit or push the human sensor. This may lead to damage or malfunction.
Do not touch the human sensor. Any scratches or dirt may lead to incorrect detection.
Do not place large objects near the human sensor. Also keep heating units outside the
sensor's detection area.
Vertical angle 90° (Side view)
7 m
90°
WARNING
CAUTION
CAUTION
Horizontal angle 100° (Top view)
7 m
50°
50°
En-2

Advertisement

Table of Contents
loading

Table of Contents