¢ External input
• "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
¢ External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to
 When indicator, etc. are connected directly
Example: Function setting 60 is set to "00"
 When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
6-1. Indoor unit
"Combination of external input and output"
Resistor
LED
Connected unit
Connected device
(Operation status)
Connected unit
on page 131.
Relay
- 130 -
Terminal
1
2
PCB
+
1
CN47
-
2
PCB
+
1
CN47
-
2
6. External input and output