Piping installation

17.2 Connecting the refrigerant piping

17.2.1 About connecting the refrigerant piping

17.2.2 Precautions when connecting the refrigerant piping

Installer and user reference guide
70
NOTICE
There are restrictions on the refrigerant pipe connection order between outdoor
units during installation in case of a multiple outdoor unit system. Install according to
following restrictions. The capacities of outdoor units A, B and C must fulfill the
following restriction conditions: A≥B≥C.
A
a b
c
a To indoor units
b Outdoor unit multi connecting piping kit (first branch)
c Outdoor unit multi connecting piping kit (second branch)
Before connecting the refrigerant piping, make sure the outdoor and indoor units
are mounted.
Connecting the refrigerant piping involves:
Routing and connecting the refrigerant piping to the outdoor unit
Protecting the outdoor unit against contamination
Connecting the refrigerant piping to the indoor units (see the installation manual
of the indoor units)
Connecting the multi-connection piping kit
Connecting the refrigerant branching kit
Keeping in mind the guidelines for:
-
Brazing
-
Using the stop valves
-
Removing the pinched pipes
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurise the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
B
C
VRV IV+ heat pump for high ambient temperatures
4P561157-1B – 2021.11
RXYTQ