SERVICE PARTS INFORMATION 5
Indoor Unit Fan Motor
Check Point : AB*14/ 18/ 24LBAJ
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
140°C
AB*18LBAJ
Read Wire
White Red
Red
Black
Red
Pink
Pink
Violet
Violet
Blue
Check Point : AR*9LUAB/ 12/ 14/ 18/ 22LUAD
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
150°C
AR*9LUAB
Read Wire
White Red
Red
Black
Red
Pink
Pink
Violet
Violet
Blue
BLUE
VIOLET
PINK
RED
Pr
BLACK
WHITE
Resistance value
291
8%
204
8%
78.5
8%
78.5
8%
182
8%
at 20°C
BLUE
VIOLET
PINK
RED
Pr
BLACK
WHITE
Resistance value
367
8%
145
8%
62.6
8%
62.6
8%
160
8%
at 20°C
AB*14LBAJ
Read Wire
White Red
Red
Black
Red
Pink
Pink
Violet
(AC)
Violet
Blue
AB*24LBAJ
Read Wire
White Red
Red
Black
Red
Pink
Pink
Violet
Violet
Blue
(AC)
AR*12/ 14/ 18/ 22LUAD
Read Wire
White Red
Red
Black
Red
Pink
Pink
Violet
Violet
Blue
02-54
Resistance value
445
8%
346
8%
80.0
8%
80.0
8%
124
8%
at 20°C
Resistance value
222
8%
175
8%
63.5
8%
63.5
8%
279
8%
at 20°C
Resistance value
90.3
8%
152
8%
42.9
8%
42.9
8%
222
8%
at 20°C