ABB cFMus TZIDC-200 Manual page 21

Digital positioner
Hide thumbs Also See for cFMus TZIDC-200:
Table of Contents

Advertisement

TZIDC-200 DIGITAL POSITIONER | CI/TZIDC-200/C-FM-US-EN REV. B
Figure 8: Mounting lever and bracket on the positioner
1. Attach the lever
6
to the feedback shaft
positioner (can only be mounted in one position due to the
cut shape of the feedback shaft).
2. Using the arrow marks
4
within the operating range (between the arrows).
3. Hand-tighten the screw
4. Hold the prepared positioner with the mount bracket
loose on the actuator so that the follower pin for the lever
enters the follower guide to determine which tap holes on
the positioner must be used for the mount bracket.
5. Secure the mount bracket
using the relevant tap holes on the positioner housing.
Tighten the screws as evenly as possible to ensure
subsequent linearity. Align the mount bracket in the oblong
hole to ensure that the operating range is symmetrical (lever
moves between the arrow marks
5
of the
, check whether the lever moves
7
on the lever.
1
with screws
2
and washers
).
4
Figure 9: Mounting on a cast iron yoke
1. Attach the mount bracket
to the cast iron yoke
or
1
still
3
Figure 6: Mounting on a columnar yoke
1. Hold the mount bracket
columnar yoke
2. Insert the U-bolts
through the holes of the mount bracket.
3. Add the washers
4. Tighten the nuts so that they are hand-tight.
Note
Adjust the height of the positioner on the cast iron yoke or
columnar yoke until the lever is horizontal (based on a visual
check) at half stroke of the valve.
2
with screw
4
1
.
in the proper position on the
3
2
.
1
from the inside of the columnar yoke
4
and nuts
5
.
21
and washer
3
2

Advertisement

Table of Contents
loading

Table of Contents