Multi split type indoor units light commercial series

Advertisement

8.4.2.3 Evaporator low temperature T2 protection
For
FSFMIF-70AE2 FSLMI-180AE2
and resume till T2>8℃
For other models:When T2<4℃ for 250s or T2<0℃ , the indoor has no capacity demand and resume till
T2>8℃
8.4.3 Dry mode
8.4.3.1 Indoor fan speed is fixed at breeze and can't be changed. The louver angle is the same as in cooling
mode.
8.4.3.2 Low indoor room temperature protection
In drying mode, if room temperature is lower than 10℃, the indoor fan will stop and not resume until room
temperature exceeds 12℃.
784.3.3 Evaporator anti-freezing protection and condenser high temperature protection are active and the
same as that in cooling mode.
8.4.3.4 The outdoor fan operates the same as in cooling mode.
8.4.4 Heating mode
8.4.4.1
Outdoor fan running rules
T 4
E
D
C
B
A
A +
:When T2<4
℃ , the indoor has no capacity demand
23