IX. TROUBLESHOOTING / PETUNJUK KETIDAK NORMALAN
SYSTEM
"AC Mode" indicator not
light.
When AC main failure and
transfer to stored mode, the
backup time is short.
When AC main failure and
transfer to stored mode, unit
cut-off immediately.
ICA
PROBLEM CAUSE
1. Main voltage <140 Vac or
>300 Vac.
2. Problem in transfer
switch control.
Low battery capacity.
1. Battery damage.
2. Problem in inverter
circuit.

SERVICE CENTRE

Jln. Pinangsia Raya I No: 22BB
Jakarta - 11120
Phone : (021) 6906020 (Hunting)
Notes :
For further information, please visit "www.icaups.co.id".
----------------------------------------------------------------------------------
Catatan :
Untuk informasi lebih lanjut, silakan kunjungi "www.icaups.co.id".
RECOMMENDED SOLUTION
1. Check your mains voltage.
2. If main voltage >140 Vac and
1. Check battery voltage.
2. Charger battery ± 10 hour by
3. Call for service.
1. Replace battery with the same
2. Call for service.
ICA
<300 Vac, call for service.
kept the main switch in on
position when AC mains
normal.
rating.