Installation instruction
Outdoor Unit
Install the Outdoor Unit
• After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt, screws or nails.
A
Connecting the Piping to Indoor
For connection joint location at outside building
Please make flare after inserting flare nut (locate at joint portion of tube assembly)
onto the copper pipe. (In case of using long piping)
Connect the piping
• Align the center of piping and sufficiently tighten the flare nut with fingers.
• Further tighten the flare nut with torque wrench in specified torque as
stated in the table.
Connecting the Piping to Outdoor
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make flare after inserting the flare nut (locate at valve)
onto the copper pipe.
Align center of piping to valve and then tighten with
torque wrench to the specified torque as stated in the
table.
Evacuation of the Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT
AND PIPES in the following procedure.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
There is no extra refrigerant in the outdoor unit for air purging.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to –76 cmHg (–0.1 MPa). Then evacuate the air approximately ten minutes.
B
SU12 Series, NU12_4 Series,
KU12 Series, YU12 Series
SU18 Series
NU12_5 Series, NU18 Series,
SU24 Series
KU18 Series, KZ18 Series,
TU18 Series, YU18 Series
NU24 Series, KU24 Series,
KZ24 Series, YU24 Series
Model
A
484 mm
513 mm
513 mm
570 mm
540 mm
Spanner or
Wrench
Do not overtighten, overtightening may cause gas leakage.
Piping size
6.35 mm (1/4")
9.52 mm (3/8")
12.7 mm (1/2")
15.88 mm (5/8")
19.05 mm (3/4")
B
C
D
102 mm
18.5 mm
260 mm
148 mm
18.5 mm
260 mm
148 mm
5.5 mm
292 mm
105 mm
18.5 mm
320 mm
160 mm
18.5 mm
330 mm
Torque
wrench
Torque
[18 N•m (1.8 kgf•m)]
[42 N•m (4.3 kgf•m)]
[55 N•m (5.6 kgf•m)]
[65 N•m (6.6 kgf•m)]
[100 N•m (10.2 kgf•m)]
23