P R E - I N S TA L L AT I O N
Find a suitable mounting location:
Mount within wiring range of the LS0 luminaire. A total of 50 ft (15 m) of cable can be used,
from the X96 Ketra controller to the last LS0 luminaire, including cabling in between luminaire
segments.
The X96 Ketra controller, a Clear Connect Type X device, must be mounted within 75 ft (22.9 m) of its
assigned gateway. The X96 must have at least two Type X devices within 25 ft (7.5 m). Within a
subnet, groups or clusters of Type X devices must not be separated by greater than 25 ft (7.5 m). The
gateway and the Type X devices assigned to it must be on the same floor.
Mount a minimum of 3 ft (1.0 m) away from interference sources in the 2.4 GHz band, including
but not limited to microwaves, wireless access points, hotspots, baby monitors, thermostats,
and voice recognizing control devices.
Do not install the controller inside a third-party enclosure. Performance of Type X devices can
severely degrade if installed inside metal enclosures.
A minimum of 2 in (51 mm) of free space is required around each side of the controller (see
Figure 1), as well as above
the faceplate.
Mount the controller in a position where it can be easily
located and accessed if service or troubleshooting is
necessary.
Ensure that the reset button and output connector can be
accessed. See Figure 2.
Ensure there is sufficient space in front of the junction box to
drive the mounting screws and attach the top cover.
Ensure that the junction box is rotated to allow the output
wiring on the controller to route towards the first LS0
luminaire.
P/N 3662841 Rev A
© 2023 Lutron Electronics Co., Inc.
Figure 1
2 in
(51 mm)
7 in
2 in
(178 mm)
(51 mm)
X96 INSTALLATION GUIDE | 5
4.5 in
(89 mm)
2 in
(51 mm)