5. Electrical work
1
B
M1 M2
TB3
B
2
M1 M2
TB3
3
B
M1 M2
Pair No.
0
TB3
D
Pair No.
0
A
BRANCH
10s
No.
DIGIT
5.6. Switch setting for high ceiling or at the time of
changing the number of air outlets (Fig. 5-9)
With this unit, the air flow rate and fan speed can be adjusted by setting the SW21
(slide switch). Select a suitable setting from the table below according to the instal-
lation location.
SW21-3
OFF
4 direction
en
SW21-4
ON
SW21-3
OFF
3 direction
SW21-4
OFF
SW21-3
ON
2 direction
SW21-4
OFF
5.7. Sensing room temperature with the built-in sen-
sor in a remote controller (Fig. 5-9)
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the air flow at a time when the heating
thermometer is OFF.
7
A
A
M1 M2
S
1
2
M1 M2
S
1
2
TB5
TB15 TB5
TB15
C
C
A
A
M1 M2
S
M1 M2
S
TB5
TB5
C
C
A
CN90
M1 M2
S
1
2
TB5
TB15
9
E
Fig. 5-8
1s
DIGIT
Fig. 5-9
TPLFYP006-030EM140✱/TPLFYP018EM141✱
Silent
Standard
SW21-1
SW21-2
SW21-1
OFF
ON
OFF
2.5 m, 8.2 ft
2.7 m, 8.9 ft
2.7 m, 8.9 ft
3.0 m, 9.8 ft
3.0 m, 9.8 ft
3.3 m, 10.8 ft
5.4. Connecting remote controller, indoor and out-
door transmission cables (Fig. 5-8)
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications about
the connecting cables, refer to the outdoor unit installation manual.
• Install a remote controller following the manual supplied with the remote controller.
• Connect the remote controller's transmission cable within 10 m, 33 ft using a
0.75 mm
(AWG18) core cable. If the distance is more than 10 m, 33 ft, use a 1.25
2
mm
junction cable.
2
MA Remote controller
1
• Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-polarized
2-wire)
• DC 9 to 13 V between 1 and 2 (MA remote controller)
M-NET Remote controller
2
• Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller. (Non-
polarized 2-wire)
• DC 24 to 30 V between M1 and M2 (M-NET remote controller)
Wireless remote controller(When installing wireless signal receiver)
3
• Connect the wire of wireless signal receiver (9-pole cable) to CN90 of indoor control-
ler board.
• When more than two units are run under group control using wireless remote
controller, connect TB15 each with the same number.
• To change Pair No. setting, refer to installation manual attached to wireless remote
controller. (In the default setting of indoor unit and wireless remote controller, Pair
No. is 0.)
Terminal block for indoor transmission cable
A
Terminal block for outdoor transmission cable (M1(A), M2(B),
B
Remote controller
C
Wireless signal receiver
D
Wireless remote controller
E
5.5. Setting addresses (Fig. 5-9)
(Be sure to operate with the main power turned OFF.)
• There are 2 types of rotary switch setting available: setting addresses 1 to 9 and
over 10, and setting branch numbers.
How to set addresses
1
Example: If Address is "3", remain SW12 (for over 10) at "0", and match
SW11(for 1 to 9) with "3".
How to set branch numbers SW14 (Series R2 only)
2
Match the indoor unit's refrigerant pipe with the BC controller's end connection
number.
Remain other than series R2 at "0".
• The rotary switches are all set to "0" when shipped from the factory. These switches
can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set them
referring to the Data Book.
Address board
A
Note:
Make sure the SW21 switch are set, otherwise problems such as not getting cool/
warm may occur.
High ceiling
SW21-2
SW21-1
SW21-2
SW21-1
OFF
ON
OFF
OFF
3.5 m, 11.5 ft
3.5 m, 11.5 ft
3.5 m, 11.5 ft
TPLFYP036-048EM140✱
Silent
Standard
SW21-2
SW21-1
SW21-2
ON
OFF
OFF
2.7 m, 8.9 ft
3.2 m, 10.5 ft
3.0 m, 9.8 ft
3.6 m, 11.8 ft
3.3 m, 10.8 ft
4.0 m, 13.1 ft
(S))
High ceiling
SW21-1
SW21-2
ON
OFF
4.5 m, 14.8 ft
4.5 m, 14.8 ft
4.5 m, 14.8 ft