Legend to Indicators
Opening the detector
Service Access – Display LEDs and Buttons
Building Technologies
Fire Safety
There are 2 modes for accessing the detector service area.
Partial access
Remove the 2 screws on the top of the detector. Slide the front cover upward until it
reaches the self locking tabs.
Full access
Remove the 2 screws on the top of the detector. Slide the front cover upward until it
reaches the self locking tabs. Grasp the cover on the sides and gently apply pres-
sure to spread the cover sides outward. This will enable the cover to be totally re-
moved
Warning: Take notice of the front panel connecting cable if fully removing the
cover.
Flow OK
If self check is OK the Flow OK LED starts flashing to indicate normal operation
Smoke OK
If self check is OK the Smoke OK LED starts flashing to indicate normal operation
Alarm
The Alarm LED flashes in the event of a smoke alarm
Normalize flow button
As each installation will require a different sampling pipe configuration, this function
is used to set the zero reference for the bargraph. This function is required to be
done during commissioning of the detector. The nominal flow value which is deter-
mined during the normalize flow period is then the zero set point value for the air-
flow monitoring during normal operation.
To use this function, use a thin tool such as a paper clip or a small jeweller's
screwdriver, place the tool into the hole and push the normalize flow button.
During the Normalization period the detector is still actively monitoring for smoke
using the default values.
3