The sequence of led pulses issued by the control box identifies
the possible types of malfunction, which are listed in the table
Tab. M.
Signal
Possible cause
No stable flame signal is detected within the safety time:
2 blinks
–
–
–
–
–
Minimum air pressure switch fails to close:
3 x blinks
–
–
–
–
–
Minimum air pressure switch does not switch, or else light present in chamber prior to ignition:
4 blinks
–
–
Loss of flame during operation:
7 blinks
–
–
–
–
10 blinks
Here below you can find some causes and the possible solutions
for some problems that could cause a failure to start or a bad
working of the burner
In most cases, an operation irregularity leads to the lighting up of
the signal inside the reset button of the control box (Fig. 4 on
page 10).
When lockout lamp lights the burner will attempt to light only after
pushing the reset button After this if the burner functions correct-
ly, the lockout can be attributed to a temporary fault.
Otherwise, if the lockout persists the cause of the fault should be
sought and the solutions shown in Tab. N put into effect.
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row. If the burner
WARNING
locks out for a third time, contact the customer
service.
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.
Faults - Possible causes - Solutions
faulty ionisation probe;
faulty gas valve;
phase/neutral connections inverted;
faulty ignition transformer;
burner not adjusted (insufficient gas).
check the intervention of the VPS lockout;
faulty air pressure switch;
air pressure switch not adjusted;
the fan motor is not working;
intervention of maximum air pressure switch.
faulty air pressure switch;
air pressure switch not adjusted.
burner not adjusted (insufficient gas);
faulty gas valve;
short-circuit between the ionisation probe and the earth.
Connection error or internal fault.
27
GB
Tab. M
20063710