DANGERS, WARNINGS AND NOTES OF CAUTION THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE.
3b) FIRING WITH GAS, LIGHT OIL OR OTHER FUELS DIRECTIVES AND STANDARDS Gas burners GENERAL European directives The burner shall be installed by qualified personnel and in compliance -Regulation 2016/426/UE (appliances burning gaseous fuels) with regulations and provisions in force; wrong installation can cause -2014/35/UE (Low Tension Directive) injuries to people and animals, or damage to property, for which the -2014/30/UE (Electromagnetic compatibility Directive)
Burner data plate Type Gas - Light oil burners For the following information, please refer to Model Year European Directives the data plate: S.Number -Regulation 2016/426/UE (appliances burning gaseous fuels) burner type and burner model: must be Output Oil Flow -2014/35/UE (Low Tension Directive) reported in any communication with the Fuel...
Page 5
PART I: SPECIFICATIONS PART I: SPECIFICATIONS BURNERS FEATURES Burner with ABS polymer (silenced) air inlet Burner with aluminium air inlet Note: the figure is indicative only Control panel with startup switch Gas valve group Cover Flange Blast tube-Combustion head group Head adjusting ring nut Air intake (aluminium or ABS) Electrical panel...
Page 6
Burners are identified by burner type and model. Burner model identification is described as follows. Type E115X Model MD. SR. BURNER TYPE E115X, E140X, E190X M - Natural gas L - LPG FUEL B - Biogas C - Town gas...
Page 8
1264 1364 1.40 1033 673 1.50 1078 718 1.65 1050 690 1.80 1050 690 BS = standard blast tube BL = long blast tube DN = gas valves size B*: SPECIAL blast tube lengths must be agreed with Cib Unigas...
Page 9
1.80 B*: SPECIAL blast tube lengths must be agreed with Cib Unigas (**) According to the gas train size and the burner type, MB-DLE or VGD valves are supplied. The "V" measure, refers to the gas filter, for burners provided with Siemens...
Page 10
PART I: SPECIFICATIONS How to read the burner “Performance curve” To check if the burner is suitable for the boiler to which it must be instal- Campo di lavoro bruciatori lled, the following parameters are needed: Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65 furnace input, in kW or kcal/h (kW = kcal/h/860);...
Page 12
Performance curve minimum Pressure in the Network / gas flow rate curves(natural gas) E115X E140X Gas rate Stm Gas rate Stm E190X Gas rate Stm E115X L- E140X Gas rate Stm Gas rate Stm...
Page 13
WARNING: the diagrams refers to natural gas. For different type of fuel please refer to the paragraph “Fuel” at the beginning of this chapter. Pressure - rate in combustion head curves (natural gas) Curves are referred to pressure = 0 mbar in the combustion chamber! E115X M-.. E140X M-.. E190X M-..
PART II: INSTALLATION PART II: INSTALLATION MOUNTING AND CONNECTING THE BURNER Transport and storage ATTENTION! The equipment must be installed in compliance with the regulations in force, following the manufac- turer’s instructions, by qualified personnel. All handling operations must be carried out with appropriate resources and qualified personnel ATTENTION: Use intact and correctly dimensioned hoisting equipment, conforms to the local regulations and health and safety regulations.
Page 16
PART II: INSTALLATION Fitting the burner to the boiler To install the burner into the boiler, proceed as follows: make a hole on the closing door of the combustion chamber as described on paragraph “Overall dimensions”) place the burner to the boiler: lift it up and handle it according to the procedure described on paragraph “Handling the burner”; place the 4 stud bolts (5), according to the burner’s drilling plate described on paragraph “Overall dimensions”;...
Page 17
PART II: INSTALLATION GAS TRAIN CONNECTIONS The diagrams show the components of the gas trai included in the delivery and which must be fitted by the installer.The diagrams are in compliance with the current laws. Gas train with valves group MB-DLE (2 valves + gas filter + pressure governor) by others by burner constructor GAS INLET...
Page 18
PART II: INSTALLATION GAS TRAIN CONNECTIONS The diagrams show the components of the gas train included in the delivery and which must be fitted by the installer.The diagrams are in compliance with the current laws. Note: the figure is indicative only ”direction”...
PART II: INSTALLATION MultiBloc MB-DLE - Assembling the gas train Note: the figure is indicative only ”direction” arrows for gas supply network installation Keys Gasket Gas filter Gas valves group Bellows unit Manual valve MULTIBLOC DUNGS Mounting Mount flange onto tube lines: use appropriate sealing agent MB-DLE 405..412 Insert MB-DLE: note position of O rings MB-DLE 415..420...
Page 20
PART II: INSTALLATION MultiBloc MBE ALLA V. FARFALLA Example of gas train MBE 501939 GAS BRUCIATORE ø185 VD-R VD-V VD-R VD-V Gas filter PGMAX PGMAX PGMI PGMIN PS pressure sensor PGCP PGCP ATTENTION: once the gas train is mounted according, the gas proving test mus be performed, according to the procedure set by the laws in force.
Page 21
PART II: INSTALLATION Mounting VD-R & PS-... ActuatorVD-V ActuatorVD-R M12 x 5 Pin The actuator VD-V does not need any adjustment (funzione ON-OFF) The actuator VD-R It must be combined with the PS sensor (include regolatore di pressione) VD-R + PS 1.
Page 22
PART II: INSTALLATION SIEMENS VGD.. Mounting positions = BS SKP1. SKP2. version with SKP2 (built-in pressure stabilizer) Siemens VGD valves with SKP actuator: The pressure adjusting range, upstream the gas valves group, changes according to the spring provided with the valve group. To replace the spring supplied with the valve group, proceed as fol- lows: - Remove the cap (T)
Page 23
PART II: INSTALLATION Integrated proving system (burners equipped with LME7x, LMV, LDU) This paragraph describes the integrated proving system operation sequence: At the beginning both the valves (EV1 and EV2) must be closed. Test space evacuating: EV2 valve (burner side) opens and keep this position for a preset time ...
Page 24
PART II: INSTALLATION BURNERS WITH INVERTER VARIANT (if provided) KOSTAL Tipo Modello XXXXX M-. MD. xx. xx. x. x. xxx. EI. XXXXX M-. MD. xx. xx. x. x. xxx. EG. LMV5 XXXXX MG. MD. xx. xx. x. x. xxx. EK. XXXXX MG.
PART II: INSTALLATION ELECTRICAL CONNECTIONS WARNING! Respect the basic safety rules. make sure of the connection to the earthing system. do not reverse the phase and neutral connections. fit a differential thermal magnet switch adequate for connection to the mains. WARNING! before executing the electrical connections, pay attention to turn the plant’s switch to OFF and be sure that the burner’s main switch is in 0 position (OFF) too.
Page 26
PART III: OPERATION PART III: OPERATION DANGER! Incorrect motor rotation can seriously damage property and injure people.WARNING: before starting the burner up, be sure that the manual cutoff valves are open and check that the pressure upstream the gas train complies the value quoted on paragraph “Technical specifications”.
PART III: OPERATION Fig. 6 - Burner front panel Abb. 1 Keys Lock-out LED Hi-flame operation LED Lo-flame operation LED “Ignition transformer operation” LED “Fan motor overload tripped” LED “EV2 opening” LED “EV1 opening” LED “Gas pressure switch signal ” LED Main switch Reset pushbutton for control box AZL..
PART III: OPERATION ADJUSTING AIR AND GAS FLOW RATES WARNING! During commissioning operations, do not let the burner operate with insufficient air flow (danger of formation of carbon monoxide); if this should happen, make the fuel decrease slowly until the normal combustion values are achieved.
Page 29
PART III: OPERATION Main page check the fan motor rotation (see related paragraph). make the safety chain enabling the system to start up the combustion cycle starts: the system will show the operating stages - Prepurging (program phase no.30) - Driving to ignition position (program phase no.36) - Ignition position (program phase no.38) - Fuel (the fuel solenoid valves open) - Flame (the flame lights up)
PART III: OPERATION the Operational Status menu provides the following items: Normal operation: by selecting this item and pressing the ENTER key, the main page is showed; press ESC to go back to the main menu. Status/Reset: it shows system errors or faults occuring / it represents the lockout reset function. Fault History: by selecting this item and pressing the ENTER key, the Lockout History will be showed about the last 21 faults occured.
Page 31
PART III: OPERATION Access w-out PW Access Serv Access OEM Access LS by means of the arrow keys, select “Access w-out pass” (access without password - user level), confirm by pressing ENTER. The other levels require password reserved to the Technical Service, to the Manifacurer, etc. The menu shown accessing without password is the following: BurnerControl RatioControl...
Page 32
PART III: OPERATION SetpointW1 SetpointW2 SD_ModOn SD_ModOff the display will show: SD_ModOn Curr:: 1.0% New: 1.0% The deafult value for this parameter is1% that is, the burner will light again at a temperature 1% lower than the set-point. Change value, if needed, by means of the arrow keys;...
PART III: OPERATION Sum/Winter Time Time EU/US choose the Summertime/Wintertime mode desired and cofirm by pressing ENTER; press ESC to exit. Set the time zone (Time EU/US) in the same way. Languages: it allows setting the current language Language Italiano Curr:: New: English...
Page 34
PART III: OPERATION to the maximum output. Manual mode To by-pass the thermal protection or not to let the buner operate in high flame stage (maximum output) after ignition, the manual mode is provided. To choose the manual mode (Manual Operation), use the SELECT arrow keys OperationalStat Operation ManualOperation...
Page 35
PART III: OPERATION Adjusting the gas valves group Multibloc MB-DLE The multibloc unit is a compact unit consisting of two valves, gas pressure switch, pres- T(VR) sure stabilizer and gas filter. The valve is adjusted by means of the RP regulator after slackening the locking screw VB by a number of turns.
PART III: OPERATION MultiBloc MBE Regulation VD-R whith PS Setting scale is „Not“ linear! Various sensors available. Output pressure according to sensor‘s measuring range. Increasing pressure Adjust the outlet pressure to the value specified by the burner or equipment manufacturer! Decreasing pressure While making outlet pressure adjustments, do not exceed a value that creates a hazardous condition to the...
Page 37
PART III: OPERATION Attention! if it is necessary to change the head position, repeat the air and fuel adjustments described above. Head adjusting The combustion head position affects the flame stability.The diffuser position must be set during the commissioning according to the regulation needs.
Page 38
PART III: OPERATION MCenter head holes gas flow regulation To adjust the gas flow, partially close the holes, as follows: loosen the three V screws that fix the adjusting plate D; insert a screwdriver on the adjusting plate notches and let it move CW/CCW as to open/close the holes; once the adjustmet is performed, fasten the V screws.
Page 39
PART III: OPERATION Calibration air and gas pressure switches The air pressure switch locks the control box if the air pressure is not the one requested. If it happens, unlock the burner by means of the control box unlock pushbutton, placed on the bur- ner control panel.
PART IV: MAINTENANCE PART IV: MAINTENANCE At least once a year carry out the maintenance operations listed below. In the case of seasonal servicing, it is recommended to carry out the maintenance at the end of each heating season; in the case of continuous operation the maintenance is carried out every 6 months.
Page 41
PART IV: MAINTENANCE Adjusting the gas valves group and removing the filter MB-DLE MB-DLE 415 - 420 B01 405..412 0 CoperFKLR GHO ¿OWro 1,3,4,6 TDSSR D YLWH * 2 AWWDFFR PLVXrDWRre 5 TDSSR D YLWH 0 0, 1, 2, 3, 4, 5 7DSSR D YLWH * Prese di pressione Prese di pressione...
Page 42
Check the electrodes position after any intervention on the combustion head. Adjust the electrodes position, according to the quotes shown othe next picture E115X EA: Ignition electrode A = 2÷3 ER: Detection electrode...
PART IV: MAINTENANCE Replacing the electrodes ATTENTION: avoid the ignition and detection electrodes to contact metallic parts (blast tube, head, etc.), other- wise the boiler’s operation would be compromised. Check the electrodes position after any intervention on the combustion head. To replace the ignition electrodes, proceed as follows: remove the burner cover disconnect the electrodes cables;...
PART IV: MAINTENANCE Burner service term - In optimal operating conditions, and with preventive maintenance, the burner can last up to 20 years. - Upon expiry of the burner service term, it is necessary to carry out a technical diagnosis and, if necessary, an overall repair. - The burner status is considered to be at its limit if it is technically impossible to continue using it due to non-compliance with safety requirements or a decrease in performance.
Page 45
PART IV: MAINTENANCE TROUBLESHOOTNG GUIDE Gas operation * No electric power supply * Restore power supply * Main switch open * Close switch * Thermostats open * Check set points and thermostat connections * Bad thermostat set point or broken thermostat * Reset or replace the thermostat * No gas pressure * Restore gas pressure...
Page 48
C.I.B. UNIGAS S.p.A. Via L.Galvani, 9 - 35011 Campodarsego (PD) - ITALY Tel. +39 049 9200944 - Fax +39 049 9200945/9201269 web site: www.cibunigas.it - e-mail: cibunigas@cibunigas.it Note: specifications and data subject to change. Errors and omissions excepted.
Page 49
CIB UNIGAS 600V CONTROLLER USER’S MANUAL COD. M12925CA Rel 1.2 08/2014 SOFTWARE VERSION 1.0x code 80379 / Edition 01 - 06/2012 1 • INSTALLATION 2 • TECHNICAL SPECIFICATIONS Display 2x4 digit green, high display 10 and 7mm Keys 4 of mechanical type (Man/Aut, INC, DEC, F) •...
Page 50
3 • DESCRIPTION OF FACEPLATE Function indicators Indication of output states Indicates modes of operation OUT 1 (AL1); OUT 2 (OPEN); OUT 3 (CLOSED) MAN/AUTO = OFF (automatic control) ON (manual control) PV Display: Indication of process variable Error Indication: LO, HI, Sbr, Err PRE-HEATING = ON (running) LO= the value of process variable is <...
5 • “EASY” PROGRAMMING and CONFIGURATION S4 Jumper THE EASY CONFIGURATION (Pro=0...12) IS SUITABLE FOR (CPU) VERSIONS WITH AL1/OPEN/CLOSED LEVEL 1 MENU P.V. / S.V. Process variable P.V. / S.V. (PV display) Work Setpoint (SV display) or control output value with controller in manual Password Local Setpoint...
Page 52
• InFo Display Information display Software version 0 No Error Self diagnostic 1 Lo error code 2 Hi 3 ERR 4 SBR OUTPUT 2 OUTPUT 3 SERIAL COMMUNICATION 0 = None 0 = None 0 = None +8 error OUT2 card recognition 1 = Relay 1 = Relay +16 error OUT3 card recognition...
Page 53
• InP Input settings S, R range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other sp. r 0 default (remote setpoint present) Def. remote setpoint range; error < 0.5% f.s. error < 0.2% f.s. (t > -150°C) range 44...1800°C;...
Page 54
• Out Output settings Select a1. r reference signal for alarm1 AL.1.r AL.x.r Variable to be compared PV (process variable) AL.1.t AL.x.t Direct (high limit) Absolute or Normal 2/3 for a1. t Inverse (low limit) relative to Symmetrical alarm 1 active setpoint (window) direct...
Page 56
ld. 1 Function of LEDs Val. Function none MAN/AUTO controller ld. 2 HOLD Selftuning enabled Autotuning enabled ld. 3 Error present Softstart running Set point gradient running Pre-heating running + 16 LED flashes if active • Lin Custom linearization for main input Step 0 beginning Display limits s.
Page 57
7 • CONSENT FOR BURNER AL1 Obtain burner consent by configuring alarm 1 as inverse deviation with positive hysteresis Hy.P and negative hysteresis Hy.n 8 • PRE-HEATING FUNCTION Enable the pre-heating function by setting parameters GS.0, Ht.0, GS.1 other than zero. It consists of three phases that are activated sequentially at firing: - Ramp 0 phase Enabled by setting GS.0 >...
Page 58
9 • ADJUSTMENT WITH MOTORIZED VALVE In an adjustment process the adjustment valve has the function of varying fuel delivery (frequently corresponding to the thermal energy introduced into the process) in relation to the signal coming from the controller. For this purpose it is provided with an actuator able to modify its opening value, overcoming the resistances produced by the fluid passing inside it.
Valve control modes With the controller in manual, the setting of parameter At.y ≥ 8 allows direct control of the valve open and close commands through the keyboard Increments and Decrements on the front seats. V0 - for floating valve without potentiometer Model V0 have similar behaviour: every manoeuvre request greater than the minimum impulse t.Lo is sent to the actuator by means of the OPEN/CLOSE relays;...
11 • MANUAL TUNING A) Enter the setpoint at its working value. B) Set the proportional band at 0.1% (with on-off type setting). C) Switch to automatic and observe the behavior of the variable. It will be similar to that in the figure: Process D) The PID parameters are calculated s follows: Proportional band Variable...
Page 61
15 • ACCESSORIES • Interface for instrument configuration Kit for PC via the USB port (Windows environment) for GEFRAN instruments configuration: KIT PC USB / RS485 o TTL Lets you read or write all of the parameters • A single software for all models •...
Page 63
21/06/2012 rev. 0 Set-up for 600V RRR0-1-T73 regulator Set up for temperature probe Pt100 (ex Siemens QAE2120 130°C max.) The regulator comes out of the factory preset with the corresponding values of the Siemens RWF40.000 and RWF50.2x Verify wiring of the sensor Regulation of the set-point = 80 It can be modified by using arrows "up"...
A1.r … A1.t 3 (operating mode AL1 =inverse-relative-normal) … rL.1 2 (AL1) rL.2 18 (open) rL.3 19 (close) A.ty 9 (type of servocontrol command) Ac.t 12 (servocontrol running time: SQN72.4…/STA12..=12; SQM40.265=30) t_Lo t_Hi t.on t.oF dE.b 0,1 (dead zone in % of end scale) 99 then push and keep pushed F until visualization of Hrd …...
Page 65
Set up for temperature probe Pt100 for high temperature (350°C max.) Verify wiring of the sensor Regulation of the set-point = 80 It can be modified by using arrows "up" and "down". By pushing F you go to parameters: Hy.P 10 (hysteresis positive for output 1 terminals 21-22 (ex Q13-Q14) Hy.n -5 (hysteresis negative for output 1 terminals 21-22 (ex Q13-Q14)
Page 66
A1.r … A1.t 3 (mode AL1 =inverse-relative-normal) … rL.1 2 (AL1) rL.2 18 (open) rL.3 19 (close) A.ty 9 (type of servocontrol command) Ac.t 12 (servocontrol running time: SQN72.4…/STA12..=12; SQM40.265=30) t_Lo t_Hi t.on t.oF dE.b 0,1 (dead zone in % of end scale) 99 then push and keep pushed F until visualization of Hrd …...
Page 67
Set up for pressure transmitter 2 wires signal 4÷20mA With pressure transmitters first we need to enable their power supply: remove the part as shown below, then, on the CPU unit, move the bridge from Pt100 to +Vt IN/OUT cards Signal selection on terminal 3 Verify wiring of the sensor...
Page 69
Set -up for thermocouples type Verify wiring of the sensor Regulation of the set-point = 80 It can be modified by using arrows "up" and "down". By pushing F you go to parameters: Hy.P 10 (hysteresis positive for output 1 terminals 21-22 (ex Q13-Q14) Hy.n -5 (hysteresis negative for output 1 terminals 21-22 (ex Q13-Q14) Keep pushing F until you see PASS, release F and through the arrows set 99, push F and visualize Pro...
Page 70
A1.r … A1.t 3 (mode AL1 =inverse-relative-normal) … rL.1 2 (AL1) rL.2 18 (open) rL.3 19 (close) A.ty 9 (type of servocontrol command) Ac.t 12 (servocontrol running time: SQN72.4…/STA12..=12; SQM40.265=30) t_Lo t_Hi t.on t.oF dE.b 0,1 (dead zone in % of end scale) 99 then push and keep pushed F until visualization of Hrd …...
Page 73
MANUAL FOR OPERATION AND CALIBRATION MODULATOR SIEMENS RWF 40…. M12905CH Rev. 07 11/09...
INSTRUMENT MOUNTING Mount the instrument using the relevant mounts as illustrated in the figure. To wire the instrument and sensors, follow the instructions given on the burner's wiring diagrams. INSTRUMENT FRONTAL PANEL Current value or value of parameter (red) Setpoint or name of parameter (green) Manual operation...
INSTRUMENT SETTINGS The instrument comes with a number of factory settings that are good for 90% of cases. However, you can set or edit parame- ters proceeding as follows 1. Setting or editing of setpoint value With the burner switched off (thermostat/pressure switch series contacts open, i.e. terminals 3-4 open), press the PGM key, holding it down for less than 2 sec..
Page 76
SCL2:lower limit for analogue input 2 (same as SCL but for input 2 - factory setting 0); SCH2:upper limit for analogue input 2 (same as SCH but for input 2 - factory setting 100); SPL: lower setpoint limit (same as SCL but for setpoint - factory setting 0); SPH: upper setpoint limit (same as SCH but for setpoint - factory setting 100);...
Page 77
TABLE 1 - "PID" PARAMETERS AND RELEVANT FACTORY SETTINGS Parameter Display Values range Factory setting Remarks Limit value for auxiliary from -1999 to 9999 Do not alter contact (*) digit Auxiliary contact switching HYST from 0 to 999.9 digit Do not alter differential (*) from 0.1 to 9999 Proportional band (*)
Page 79
TABLE 3 - CONFIGURATION C112 Red display 1^ digit 2^ digit 3^ digit 4^ digit Auxiliary limit switch K6 none lk1 function for input 1 lk2 function for input 1 lk3 function for input 1 lk4 function for input 1 lk5 function for input 1 lk6 function for input1 lk7 function for input 1...
Page 80
TABLE 4 - CONFIGURATION C113 Red display 1^ digit 2^ digit 3^ digit 4^ digit Instrument addresses (for RWF 40.003 only address 0 address 1 address... address 99 Unit of measurement and decimal place °C without decimal °C and 1 decimal °F without decimal °F and 1 decimal Activation of “K6”...
Page 82
Probe electric connection : With 7 pins connector version With terminals version TRASDUCER PASSIVE TRASDUCER PASSIVE CONNECTION ONLY CONNECTION ONLY TRASDUCER PASSIVE TRASDUCER PASSIVE CONNECTION ONLY CONNECTION ONLY...
Page 83
With external setpoint C111 configuration code = X1X1 With setpoint modified by independent management system C111 configuration code = X9XX SCH2= 0.5x (SPH - SPL) SCL2= -0.5 x (SPH - SPL) Example: SPH= max. 130° C SPL= min. 30° C SCH2= 0.5 x (130 - 30) = 50 SCL2= -0.5 x (130 - 30) = -50...
Page 84
APPENDIX: PROBES CONNECTION To assure the utmost comfort, the control system needs reliable information, which can be obtained provided the sensors have been installed correctly. Sensors measure and transmit all variations encountered at their location. Measurement is taken based on design features (time constant) and according to specific operating conditions. With wiring run in raceways, the sheath (or pipe) containing the wires must be plugged at the sensor's terminal board so that currents of air cannot affect the sensor's measurements Ambient probes (or ambient thermostats)
Page 85
Duct or pipe sensors Installing pressure sensors Installing temperature sensors A - installation on ducts carrying fluids at max. temperature For measuring outlet air: 80°C B - installation on ducts at temperature over 80°C and for refri- after delivery fan or gerants after coil to be controlled, at a distance of at least 0,5 m C - installation on ducts at high temperatures:...
Page 86
Immersion or strap-on sensors Immersion probes mounting Sensors must be installed on the stretch of pipe in which fluid circulates all the time. The rigid stem (sensing element doing the measuring) must be inserted by at least 75mm and must face the direction of flow.
Page 87
Duct pressure switches and sensors Installing differential pressure probes for air Basic principles Measuring static pressure (i.e. pressure exerted by air on pipe walls) A - Control a filter (clogging) Measuring dinamic pressure B - Control a fan (upstream/downstream) kg/m3, specific weight of air m/s, air speed 9.81 m/s2, gravity acceleration mm C.A., dynamic pressure...
Page 88
Spare parts Description Code Modulator RWF40.000 2570112 Adapting frame Siemens ARG40 from RWF32.. to RWF40.. 2570113 Temperature probe Siemens QAE2120.010A (30÷130°C) 2560101 Temperature probe Siemens QAM2120.040 (-15÷+50°C) 2560135 Thermoresistor Pt1000 ø = 6mm L = 100mm (30÷130°C) 2560188 Thermoresistor Pt1000 ø = 10mm L = 200mm (0÷350°C) 2560103 Pressure probe Siemens QBE2..
Page 89
RWF50.2x & RWF50.3x User manual M12922CB Rel.1.0 07/2012...
DEVICE INSTALLATION Install the device using the relevant tools as shown in the figure. To wire the device and sensors, follow the instructions on the burner wiring diagram.
FRONT PANEL NAVIGATION MENU Parameter level Basic display User Level - Opr SP1 or SP2 (editable) dSP readable and editable through bin1 = 2 InP1 or y (only display) Parameter Level - PArA HYS1 , HYS2 , HYS3 Pb1, dt, rt, db, tt Next parameter Main navigation...
Page 92
RWF5 is preset good for 90% of applications. However, you can set or edit parameters as follow: Set-point: set or modification: When the burner is in stand-by, (safety loop open, that is terminals 3-4/T1-T2 on the 7 pole plug open) push the Enter button: on the lower display (green) Opr appears;...
Page 93
Setting the kind of sensor to be connected to the device: push the Enter button: on the lower display (green) Opr appears. Using the up and down arrows find ConF. Push Enter to confirm. Now on the green display the group InP appears. Push Enter and InP1 is displaied. Enter to confirm. ...
Page 94
ConF > Cntr Parameter Value Description CtYP 1 = 3-position controller (open-stop-close only RWF50.2) controller type 2 = continuative action controller (only RWF50.3) CACt 1 = heating controller control action 0 = cooling controller least value of the set-point limitation prevents entry of values outside the defined set-point range -1999..0..+9999 range...
Page 95
ConF > OutP (parameter under group only for RWF50.3) Parameter Value Description FnCt 1 = analog input 1 doubling with possibility to convert tipo di controllo (depending on par SiGn) 4 = modulation controller SiGn physical output signal (terminals A+, A-) type of output signal 0 = 0÷20mA 1 = 4÷20mA...
Page 96
Manual control : in order to manual change the burner load, while firing keep pushing the ESC button for more than 5 s; on the lower green display Hand appears. using the UP and DOWN arrows, the load varies. ...
Electric connection : With 7 pins connector version With terminals version Matches terminals between RWF50.2 and RWF40.0x0...
Page 98
Parameters summarising for RWF50.2x: Conf Conf Navigation menù Inp1 Cntr diSP PArA Types of probe SEn1 OFF1 SCL1 SCH1 Unit dECP Pb. 1 dt HYS1 (*) HYS3 (*) SP1 (*) Siemens QAE2120… needless needless 80 350 (#) 80 °C Siemens QAM2120.. needless needless 80 350 (#)
Page 99
APPENDIX: PROBES CONNECTION To assure the utmost comfort, the control system needs reliable information, which can be obtained provided the sensors have been installed correctly. Sensors measure and transmit all variations encountered at their location. Measurement is taken based on design features (time constant) and according to specific operating conditions.With wiring run in raceways, the sheath (or pipe) containing the wires must be plugged at the sensor's terminal board so that currents of air cannot affect the sensor's measurements.
Page 100
Duct or pipe sensors Installing pressure sensors A - installation on ducts carrying fluids at max. temperature 80°C Installing temperature sensors For measuring outlet air: B - installation on ducts at temperature over 80°C and for refrigerants after delivery fan or C - installation on ducts at high temperatures: ...
Page 101
Immersion or strap-on sensors Immersion probes installation Sensors must be installed on the stretch of pipe in which fluid circulates all the time. The rigid stem (sensing element doing the measuring) must be inserted by at least 75mm and must face the direction of flow. Recommended locations: on a bend or on a straight stretch of pipe but tilted by 45°...
Page 102
Duct pressure switches and sensors Installing differential pressure probes for air Basic principles Measuring static pressure(i.e. pressure exerted by air on pipe walls) A - Control a filter (clogging) Measuring dinamic pressure B - Control a fan (upstream/downstream) Kg/m , specific weight of air m/s, air speed 9.81 m/s gravity acceleration...
Page 107
M12927CA DISPLAY Y AND KEY onsent to the burner is rned off OUTP UT LEDs ON (o out1) - Consen nt to the burne ▲ - (o out2) Output i ncrease ▼ - (o out3) Output d decrease ● - (ou ut4) Modulato r is powered o perator Mode...
M12927CA CONNECTIONS DIAGRAM Probe connection: • PT1000/NTC/PTC: between terminal 3 and 2 • PT 100: between terminal 3 and 2 with terminal 1 • Passive pressure probe 0/4-20 mA: between terminal 4 ( + ) e 1 ( - ) Note: out4 must be activated ( IO4F must be setted to ON ) •...
M12927CA SETPOINT AND HYSTERESIS CONFIGURATION (SP, AL1, HAL1 parameters) Push the button to enter into the setpoint configuration: SP setpoint value change: increase decrease 2480 Confirm / Next AL1 parameter value change: increase decrease Confirm / Next HAL1 HAL1 parameter value change: increase decrease Confirm / Next Back to the first parameter To return to normal mode, press the key for 3 seconds or wait the 10s timeout...
Page 110
M12927CA LIMITED ACCESS LEVEL Proceed as follows to change some parameters that are not visible in standard user mode: Press the key for Password = 20 3 seconds Access to parameter: Increase the displayed value Decrease the displayed value Confirm and go to next parameter Param Description...
M12927CA CONFIGURATION How to access configuration level The configuration parameters are collected in various groups. Every group defines all parameters related with a specific function (e.g.: control, alarms, output functions). Push the button for more than 5 seconds. The upper display will show PASS while the lower display will show 0.
Page 113
M12927CA Safety output value -100... 100 io4.F I/O4 function selection on = Out4 will be ever ON (used as a transmitter power supply) ,out4 = Uscita 4 (Used as digital output 4), dG2c = Digital input 2 for contact closure, dG2U = Digital input 2 driven by 12... 24 diF1 Digital input 1 function oFF = Not used,...
Page 114
M12927CA windows SE.br = Sensor Break LodE = Deviation low alarm (relative) HidE = Deviation high alarm (relative) LHdo = Relative band alarm in alarm out of the band LHdi = Relative band alarm in alarm inside the band Alarm 1 function 0...
Page 115
M12927CA AL3 Group - alarm 3 parameters Param Description Values Liv N° Default AL3t Alarm 3 type nonE = Alarm not used nonE LoAb = Absolute low alarm HiAb = Absolute high alarm LHAo = Windows alarm in alarm outside the windows LHAI = Windows alarm in alarm inside the windows...
Page 116
M12927CA SELF Self tuning enabling no = The instrument does not perform the self- tuning YES = The instrument is performing the self- tuning Proportional band 1... 9999 (E.U.) page 7 Integral time 0 (oFF) ... 9999 (s) page 7 Derivative time 0 (oFF) ...
Page 117
M12927CA AAc = Alarm reset ASi = Alarm acknowledge chSP = Sequential set point selection St.by = Stand by mode. The first press puts the instrument in stand by mode while a second one puts the instrument in Auto mode. Str.t = Timer run/hold/reset P.run = Program run P.rES = Program reset...
Page 118
M12927CA con Group - Consumption parameters Param Description Values N° Default Co.tY Count type oFF = Not used 1 = Instantaneous power (kW) 2 = Power consumption (kW/h) 3 = Energy used during program execution. This measure starts from zero when a program runs end stops at the end of the program.
M12927CA OPERATIVE MODES When the instrument is powered, it starts immediately to work according to the parameters values loaded in its memory. The instrument behaviour and its performance are governed by the value of the stored parameters. At power ON the instrument can start in one of the following mode depending on its configuration: Automatic Mode In Automatic mode the instrument drives automatically the control output according to the parameter value set and the set point/measured value.
M12927CA Direct set point modification This function allows to modify rapidly the set point value selected by [83] A.SP (selection of the active Set point) or to the set point of the segment group (of the programmer) currently in progress. Push button.
M12927CA ERROR MESSAGES The upper display shows the OVER-RANGE and UNDERRANGE conditions with the following indications: Over-range: Under-range The sensor break will be signalled as an out of range: Note: When an over-range or an under-range is detected, the alarms operate as in presence of the maximum or the minimum measurable value respectively.
Page 122
RWF55.5X & RWF55.6X User manual M12926CA Rel.0.1 10/2015...
Page 123
DEVICE INSTALLATION Fixing system Drilling dimensions:...
Page 124
FRONT PANEL Burner release Controlling element CLOSED/stage 1 Controlling element OPEN/stage 2 Operating mode 2-stage Actual value display (red) and parameter value USB led Comunication via interface Operating mode 2-stage Thermal shock protection Alarm function Decrease value Increase value ESC button Enter button...
Page 125
NAVIGATION MENU User Level - Opr Parameter level SP1 or SP2 (editable) dSP readable and editable through bin1 = 2 InP1 or y (only display) Basic display Parameter level - PArA Pb1, dt, rt, db, tt Heating controllerHYS1 , HYS2 , HYS3 Cooling controller HYS4 , HYS5 , HYS6...
Page 126
PID parameters set and modifications (PArA): Push Enter button, on the green display Opr appears; using the down arrow, scroll until group PArA is reached and push Enter. On the green display Pb1 e appears and on the red one the set parameter. Push is sequence the down or up arrow the menu is scrolled. Push Enter to select and the arrows to choose the desired value.
Page 127
Setting the kind of sensor to be connected to the device: Push the Enter button: on the lower display (green) Opr appears. Using the up and down arrows find ConF. Push Enter to confirm. Now on the green display the group InP appears. Push Enter and InP1 is displaied. Enter to confirm.You are inside InP1; the green display shows Sen1 (sensor type), while the red display shows the chosen sensor code Push Enter to enter the Sen1 parameter, then choose the desired sensor using the arrows.
Page 128
ConF > InP >InP2 Input 2 : this input can be used to specify an external setpoint or carry out setpoint shifting Parameter Value Description no function FnC2 external setpoint (display SPE) setpoint shifting (display dSP) angular positioning feedback SEn2 0 ÷...
Page 129
ConF > Cntr Here, the type of controller, operating action, setpoint limits and presettings for self-optimization are selected Parameter Value Description CtYP 3-position controller (open-stop-close) ontroller type continuative action controller (0 ÷10V 4 ÷ 20mA) heating controller CACt control action cooling controller minimum set-point scale -1999..0..+9999...
Page 130
Alarm functionAF The alarm function can be used to monitor the analog inputs. If the limit value is exceeded, multifunctional relay K6 (terminals 6N and 6P) is activated (depending on the switching characteristic) The alarm function can have different switching functions (lk1 to lk8) and can be set to a deviation from the active setpoint or to a fixed limit value Limit value AL relative to setpoint (x) Fixed limit value AL...
Page 131
ConF > AF Parameter Value Description FnCt Without function type of control monitored input Ik1 = InP1 monitored input Ik2 = InP1 monitored input Ik3 = InP1 monitored input Ik4 = InP1 monitored input Ik5 = InP1 monitored input Ik6 = InP1 monitored input Ik7 =...
Page 132
ConF > binF This setting decides on the use of the binary inputsD1, D2, DG Parameter Value Description without function bin1 binary imput terminals set-point changeover (SP1 / SP2) – D1) set-point shift (Opr > dSP parameter = value of set-point modify) 2 = l input alarm changeover of operating mode...
Page 133
ConF > IntF The controller can be integrated into a data network using an optional RS-485 (terminals R+ and R-) interface or an optional Profibus DP interface(only modelRWF55.6x terminalsC1-C2-C3-C4) Parameter Value Description bdrt 0 = 4800 baud baudrate 1 = 9600 baud 2 = 19200 baud 3 = 38400 baud Address in the data network...
Page 134
Display of software version : The software version is shown by pushing Enter + UP arrow on the upper display Weather-compensated setpoint shifting(climatic regulation): The RWF55 can be configured so that weather-compensated setpoint shifting is activated when an LG-Ni1000 outside sensor or a Pt1000 is connected (see parameter InP3).
Page 135
Modbus interface The tables that follow in this chapter specify the addresses of the readable and writable words that the customer is able to access. The customer may read and/or write the values using SCADA programs, PLCs, or similar. The entries under Access have the following meanings: R/O Read Only, value can only be read R/W Read/Write, value can be read and written The number of characters specified under Data type in the case of character strings includes the final \0.
Page 136
Configuration level Address Access Data type Signal reference Parameter 0x3426 Float SCL1 Start of display input 1 0x3428 Float SCH1 End of display input 1 0x3432 Float SCL2 Start value input 2 0x3434 Float SCH2 End value input 2 0x3486 Float Start of setpoint limitation 0x3488...
Page 137
Dati dell’apparecchio Address Access Data type Signal reference Parameter 0x8000 Char12 Software version 0x8006 Char14 VdN number Stato dell’apparecchio Address Access Data type Signal reference Parameter 0x0200 Word Outputs and states Bit 0 Output 1 Bit 1 Output 3 Bit 2 Output 2 Bit 3 Output 4...
Electric connections : With 7 pins connector version With terminals version Corrispondences bornes entre RWF55.5x y RWF40.0x0Matches terminals betweenRWF55.5x and RWF40.0x0...
Page 139
Parameters summarising for RWF55.xx : ConF ConF Navigation menù Inp1 Cntr diSP PArA Types of probe SEn1 OFF1 Unit dECP Pb. 1 HYS1 (*) HYS3 (*) SP1 (*) ...
Page 140
APPENDIX: PROBES CONNECTION To assure the utmost comfort, the control system needs reliable information, which can be obtained provided the sensors have been installed correctly. Sensors measure and transmit all variations encountered at their location. Measurement is taken based on design features (time constant) and according to specific operating conditions.With wiring run in raceways, the sheath (or pipe) containing the wires must be plugged at the sensor's terminal board so that currents of air cannot affect the sensor's measurements.
Page 141
Duct or pipe sensors Installing pressure sensors Installing temperature sensors A - installation on ducts carrying fluids at max. temperature 80°C For measuring outlet air: B - installation on ducts at temperature over 80°C and for refrigerants "after delivery fan or C - installation on ducts at high temperatures : "after coil to be controlled, at a distance of at least 0,5 m ·"increase length of siphon...
Page 142
Immersion or strap-on sensors Immersion probes installation Sensors must be installed on the stretch of pipe in which fluid circula- tes all the time. The rigid stem (sensing element doing the measuring) must be inser- ted by at least 75mm and must face the direction of flow. Recommended locations: on a bend or on a straight stretch of pipe but tilted by 45°...
Page 143
Duct pressure switches and sensors Installing differential pressure probes for air Basic principles Measuring static pressure(i.e. pressure exerted by air on pipe walls) A - Control a filter (clogging) Measuring dinamic pressure B - Control a fan (upstream/downstream) Legend Kg/m3, specific weight of air m/s, air speed 9.81 m/s2 gravity acceleration mm C.A., dynamic pressure...
Page 145
Note: Specifications and data subject to change. Errors and omissions excepted.