Mitsubishi Electric s-MEXT-G00 006-044 Operation Manual page 16

Computer room air conditioner
Table of Contents

Advertisement

UM_s-MEXT_ME28relC_00_12_19_ML
Mask of the terminal
--------------- P50.01
Set point cooling:
24.0 °C
--------------- P50.02
Set point heating:
24.0 °C
--------------- P50.03
Set point dehumidif.
55%RH
--------------- P50.04
Set point humidif.:
45%RH
--------------- P50.05
Set point cooling by
LAN limits:
30.0°C
--------------- P50.06
Set point heating by
LAN limits:
18.0°C
--------------- P50.07
Set point dehumdif. by
LAN limits:
75%RH
--------------- P50.08
Set point humdif. by
LAN limits:
35%RH
--------------- P50.09
MIN room temperature
for deumid OFF: 23.0°C
Clock
Clock card
not installed
Clock config.:
Date
Tme
01/05/13
10:40
Time bands
not enabled.
See user menu
USER MANUAL
Description of the mask
Parameters to set the cooling and heating set points, if the hot sources are enabled
Parameters to set the dehumidifier and humidifier set points
Parameters to set the cooling set point by LAN limits and heating set point by LAN limits
Parameters to set the dehumidifier set point by LAN limit and humidifier set point by LAN limits
Parameters for minimum room temperature and dehumidifier off
Mask confirming access to the Clock menu.
Press "Up" or "Down" to scroll through the other masks and "Esc" to return to the menu selection list.
Submenu that can be used to adjust the internal clock and configure the time bands.
Mask indicating the lack or damage to the clock board.
Current date and time setting.
Indicates that the time bands have been set correctly, though they are not enabled. To enable them, see user
menu.
TRANSLATION OF THE ORIGINAL INSTRUCTIONS