Mitsubishi Electric s-MEXT-G00 006-044 Operation Manual page 14

Computer room air conditioner
Table of Contents

Advertisement

UM_s-MEXT_ME28relC_00_12_19_ML
Icon
SAFETY REDUCTION LOAD
(LP) ACTIVATED
POST-VENTILATION
ACTIVATED
DELAY FOR TIME
OBSERVATION
HIGH TEMPERATURE pLAN
RESCUE ACTIVATED
LOW TEMPERATURE pLAN
RESCUE ACTIVATED
HIGH HUMIDITY pLAN
RESCUE ACTIVATED
LOW HUMIDITY pLAN
RESCUE ACTIVATED
HOT SPOT PROTECTION
ACTIVATED
COLD SPOT PROTECTION
ACTIVATED
ACTIVE FAN ON STAND-BY
ACTIVATED
PERIODIC CHECK
FAN ACTIVE FOR GAS
BUILD-UP PREVENTION
FAN BOOST
BY ALARM IN THE LAN
EXTERNAL UNIT STOPPED
BY ALARM IN THE LAN
FC DAMPER OPENED
BY ALARM IN THE LAN
Note: All the active functions of the unit are displayed in the same mask (with the flashing of various icons).
USER MANUAL
Function
Safety Reduction Load LP
Post-ventilation active
Delay for time obs.
High temperature pLAN
rescue active
Low temperature pLAN
rescue active
High humidity pLAN rescue
active
Low humidity pLAN rescue
active
Hot Spot protection for a
pLAN network
Cold Spot protection for a
pLAN network
Active Fan on Standby
Periodic override
Ventilation active for gas
build-up prevention
Forcing of ventilation to
maximum level due to a LAN
alarm
External unit stopped due to
a LAN alarm
Direct Free Cooling damper
open to maximum level due
to a LAN alarm
Meaning
The Safety Reduction Load LP (low pressure) function is enabled. The internal
fan of the unit and the inverter are controlled to prevent excessively low pressure
in the low pressure section.
The heater cooling post-ventilation is active
One or more compressors are blocked to comply with the start-up times, or the
unit is awaiting regulation
The pLAN network logics activate the unit when the high temperature limit is
exceeded.
The pLAN network logics activate the unit when the low temperature limit is
exceeded.
The pLAN network logics activate the unit when the high humidity limit is
exceeded.
The pLAN network logics activate the unit when the low humidity limit is
exceeded.
The unit considers its local temperature instead of the average temperature to
control the Hot Spot concerned.
The unit considers its local temperature instead of the average temperature to
control the Cold Spot concerned.
The unit is on standby but the fan continues to run at a set speed
The unit forces the cooling demand sent to the PAC-IF cards to minimum and
keeps ventilation at maximum to help prevent the formation of ice on the piping.
The unit is off, but the fans are kept in operation at reduced speed to prevent gas
build-up in case of leaks
Ventilation has been forced to maximum level due to an alarm (no air flow or gas
leak detected) in one of the other units connected to the LAN network
The Mr Slim external unit has been stopped due to an alarm (gas leak detected)
in one of the other units connected to the LAN network
The Direct Free Cooling damper has been opened to maximum level due to an
alarm (gas leak detected) in one of the other units connected to the LAN network
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
40