OPERATING PROCEDURE
13. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 2 cover panel (front) fixing screws (5 × 12) and
remove the cover panel (front). (See Photo 3-1)
(4) Remove 2 cover panel (rear) fixing screws (5 × 12) and
remove the cover panel (rear).
(5) Remove the electrical parts box. (See Photo 3-2)
(6) Remove the valve bed. (Refer to procedure 9)
(7) Remove the side panel (R). (Refer to procedure 9)
(8) Remove 3 separator fixing screws (4 × 10) and remove
the separator.
(9) Remove the soundproof cover for compressor.
(10) Recover refrigerant.
(11) Remove the welded pipe of compressor inlet and outlet
then remove the compressor.
(12) Remove the 3 points of compressor fixing nut using a
spanner or an adjustable wrench.
Note: Recover refrigerant without spreading it in the air.
14. Removing the power receiver
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the cover panel (front). (Refer to procedure 13)
(4) Remove the cover panel (rear). (Refer to procedure 13)
(5) Remove the electrical parts box. (See Photo 3-2)
(6) Remove the valve bed. (Refer to procedure 9)
(7) Remove the side panel (R). (Refer to procedure 9)
(8) Recover refrigerant.
(9) Remove 4 welded pipes of power receiver inlet and outlet.
(10) Remove 2 receiver leg fixing screws (4 × 10).
Note: Recover refrigerant without spreading it in the air.
OCH755
PHOTOS/FIGURES
Photo 11
Valve bed
Separator
Separator
fixing screw
Compressor
fixing nuts
79
Valve bed
fixing
screws
Power
receiver
Compressor
(MC)