OPERATING PROCEDURE
12. Removing the reactors (ACL1, ACL2, ACL3)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the 6 screws, screw 8 and 9 (5 × 12), that fix
the front panel and remove the front panel. (See Photo 3)
(4) Remove the 2 screws, screw 0 and 1 (both 4 × 10), that
fix the separator, screw 0 from the valve bed and screw
1 from the bottom of the separator, and tilt the separator
to the side of the fan motor slightly.
(See Photo 10-1 and 10-2)
(5) Disconnect the lead wires from the reactor and remove
the 4 screws, screw 2, that fix the reactor to remove the
reactor. (See Photo 10-3 and 10-4)
Note 1: The reactor is very heavy (4kg)!
Be careful when handling it.
Note 2: The reactor box is also removable.
Photo 10-2
Reactor box
Separator
Photo 10-3
Propeller
Reactor box
Reactors
OCH755
Photo 10-1
Front panel
Photo 10-4
Screw1
4-way
valve
Reactor box
78
PHOTOS/FIGURES
Controller circuit board
Screw
(C.B.)
8
Screws
9
Screws2
Electrical
parts box
Noise filter
circuit board
(N.F.)
Terminal
block (TB2)
Terminal
block (TB1)
Valve bed
Screw
0
Compressor
(MC)
Terminal
cover

Advertisement

Table of Contents
loading

Table of Contents