7.4. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping
air tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning
on the power.
Function details
Function
Function
Setting number
number
00
Standard
Filter
01
Longer
indicator
11
interval
02
Shorter
00
Enable
01
Disable
Filter
indicator
13
Display only
action
on central
02
remote con-
troller
00
Standard
Cool air
01
Adjust (1)
temperature
30
trigger
02
Adjust (2)
00
Standard
01
Adjust (1)
Heat air
temperature
31
02
Adjust (2)
trigger
03
Adjust (3)
00
Enable
Auto restart
40
01
Disable
00
Super low
Cool Air
Follow the
43
setting on
Prevention
01
the remote
controller
00
Start/Stop
Emergency
External
01
46
stop
control
02
Forced stop
00
All
Error report
Display only
47
target
on central
01
remote
controller
Follow the
setting on
Fan set-
00
the remote
ting when
controller
cooling
49
thermostat
OFF
01
Stop
(Forbidden)
60
00
(Forbidden)
61
00
(Forbidden)
62
00
(Forbidden)
70
00
Details
Default
Adjust the fi lter cleaning
interval notifi cation. If the
notifi cation is too early,
change to setting 01. If the
notifi cation is too late, change
to setting 02.
Enable or disable the fi lter
indicator. Setting 02 is for
use with a central remote
controller.
Adjust the cool air trigger
temperature. To lower the
trigger temperature, use
setting 01. To raise the trigger
temperature, use setting 02.
Adjust the heat air trigger
temperature. To lower the
trigger temperature by 6
degrees C, use setting 01. To
lower the trigger temperature
by 4 degrees C, use setting
02. To raise the trigger tem-
perature, use setting 03.
Enable or disable automatic
system restart after a power
outage.
Restrain the cold airfl ow
with making the airfl ow
lower when starting heating
operation. To correspond to
the ventilation, set to 01.
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor
unit stops by the input to
the external input terminals,
and Start/Stop by a remote
controller is restricted.
Change the target for report-
ing errors. Errors can either
be reported in all locations,
or only on the central remote
controller.
When set to 01, the fan stops
when the thermostat is OFF
in cooling operation. Con-
nection of the wired remote
controller (2-wire type or
3-wire type) and switching its
thermistor are necessary.

8. TEST RUN

8.1. Test run using Outdoor unit (PCB)

• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.

8.2. Test run using Remote Controller

• Refer to the Installation Manual for the remote controller to perform the test run using
the wireless remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps
fl ash slowly at the same time.
For details, please refer to the Manual of "IR Receiver Unit" or "Wired Remote Controller".

9. CHECK LIST

Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
CHECK ITEMS
Has the indoor unit been installed
correctly?
Has there been a check for gas leaks
(refrigerant pipes)?
Has heat insulation work been
completed?
Does water drain easily from the indoor
units?
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
Are the wires and pipes all connected
completely?
Is the indoor unit earthed (grounded)?
Is the connection cable the specified
thickness?
Are the inlets and outlets free of any
obstacles?
Does start and stop air conditioner
operation by remote controller
or external device?
After installation is completed, has the
proper operation and handling been
explained to the user?
CHECK
If not performed correctly
BOX
Vibration, noise,
indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn
damage
No operation, heat or burn
damage
Short circuit
No operation, heat or burn
damage
No cooling, No heating
No operation
En-16