5-6. Selecting A Location And Connecting Input Power

18 in (457 mm) of
space for airflow
Y Do not move or operate
unit where it could tip.
=GND/PE Earth Ground
1
6
3
4
10
1
8
L2
230 VAC, 1
Y Special installation may be
required where gasoline or
volatile liquids are present −
see NEC Article 511 or CEC
Section 20.
Y Installation must meet all Na-
tional and Local Codes −
have only qualified persons
make this installation.
Y Disconnect and lockout/tag-
out input power before con-
necting input conductors
from unit.
Y Always connect green or
green/yellow conductor to
supply grounding terminal
first, and never to a line ter-
minal.
1
Rating Label
Supply correct input power.
2
Black And White Input
Conductor (L1 And L2)
3
Green Or Green/Yellow
Grounding Conductor
4
Input Power Cord.
5
Disconnect Device (switch
9
shown in the OFF position)
6
Disconnect Device Grounding
Terminal
5
7
Disconnect Device Line
Terminals
7
Connect green or green/yellow
L1
grounding conductor to disconnect
2
device grounding terminal first.
L2
Connect input conductors L1 and
L2 to disconnect device line
terminals.
8
Receptacle (NEMA 6-50R)
Connect receptacle as shown.
9
Over-Current Protection
Select type and size of over-current
protection using Section 5-7 (fused
disconnect switch shown).
Close and secure door on disconnect
device.
Remove
device, and place switch in the On
position.
10 Plug (NEMA 6-50P)
L1
Connect plug to receptacle.
ssb2.2* 1/94 − 804 622-A
OM-228 187 Page 15
lockout/tagout