T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
PROGRAM
RELAY 1
SENSOR
Fig. 32. Program - Sensor.
PROGRAM
RELAY 1
HEAT/COOL
Fig. 33. Program - Heat/Cool.
PROGRAM
RELAY 1
SETBACK
Fig. 34. Program - Setback.
62-0254—13
MENU
PROGRAM
RELAY 1
SENSOR
SENSOR A
SENSOR B
SELECT
SENSOR FOR
RELAY 1
M24496
MENU
PROGRAM
RELAY 1
HEAT/COOL
HEAT
COOL
SELECT
HEAT/COOL
FOR
RELAY 1
M24497
MENU
PROGRAM
RELAY 1
SETBACK
60
o
F
ENTER
SETBACK
SETPOINT
FOR RELAY 1
M24498
16
1.2.3. SENSOR
1. From the menu, use the
highlight SENSOR.
2. Press the
button to display the sensor selec-
tions.
3. Use the
and
B.
4. Press the
button to accept the highlighted sen-
sor and display the next option.
1.2.4. HEAT/COOL
1. From the menu, use the
highlight HEAT/COOL.
Default: HEAT
2. Press the
button to display the heat and cool
selections.
3. Use the
and
4. Press the
button to accept the highlighted
selection and display the next option.
1.2.5. SETBACK
The Setback temperature option displays if scheduling is
enabled (See Fig. 57 on page 24) or the DI Option is set
to Setback. (See Fig. 60 on page 26).
This is the desired setpoint temperature that you want to
use during setback mode for this output. For example, if
your setpoint is 70° F (21° C) and you want the
temperature to drop 10° F during setback mode, enter
60° F (16° C) as the setpoint for this output.
1. From the menu, use the
highlight SETBACK.
2. Use the
and
the desired setpoint temperature.
Default: 60° F (16° C)
Range: -40° to 248° F (-40° to 120° C)
3. Press the
button to accept the value and display
the menu.
1.2.6. Program Next Output
For the next output (Mod or Relay), select the desired
output from the Program menu (Refer to Fig. 28 on
page 14).
Go to "1.2.1. SETPOINT" on page 15 to program the next
output.
When you finish programming the outputs, continue with
"1.2.7. Exiting Program Mode" on page 17.
and
buttons to
buttons to select Sensor A or
and
buttons to
buttons to select Heat or Cool.
and
buttons to
buttons to increase/decrease
(Mod or Relay)