SECTION J:

FUELING

WARNING: Use only ASTM D3699 1-K kerosene or ASTM D396 No.1 S500 Low Sulfur No.1 Fuel Oil. NEVER USE GASOLINE.
Use of gasoline can lead to uncontrollable flames resulting in destructive fire.
¡ Large Capacity External Tank
Tank must be purchased separately and installed by a qualified fuel supply technician.
NOTE: External tank installation must comply with National Fire Protection Association Code NFPA 31, CSA
standard B139, the Installation Code for Oil Burning Equipment, or locally applicable codes. Check
with local building officials.
The following instructions should be followed for installation of a large capacity, gravity-fed external fuel tank.
¡Installation height of tank's fuel outlet should be at least 16 in. above floor surface upon which
heater rests.
¡To avoid excess fuel pressure to heater, top of fuel tank should be no more than 8-1/2 ft. above
floor surface upon which heater rests.
¡Fuel tank should be located at least 6 ft. away from all heat sources.
¡3/8" OD copper tubing should be used for fuel line.
¡To prevent air locks in fuel line, fuel line should be smooth with no U-shaped or sharp bends.
¡Use of fuel filter in fuel line adjacent to tank is recommended, shut-off valves should also be
installed on the fuel line and connected to the tank as shown below.
NOTE: An additional shut-off valve installed next to the exterior wall will minimize fuel to be drained should
heater have to be disconnected. If the valve is on interior side, a fusible link type is recommended.
1. Be sure all external tanks have an operating vent.
2. The use of a water trap filter is recommended. A model with a drain plug or petcock is preferred.
3. Be sure to observe the maximum and minimum tank heights as specified.
NOTE: If the maximum height from the top of the fuel tank to the bottom of the heater exceeds 8-1/2 ft., a
fuel pressure reducing valve, preset at 2.5 psi, is required .
Pressure Reducing Valve Part#10005099 has 3/8 in. (N.P.T.) inlet and outlet female openings to accept
the fuel line fittings.
NOTE: Fusible Link Valve (#10005597)
¡It is most important that the valve, depending on its use, be fully opened or fully closed.
¡The top nut on the valve (below the turn handle) is sealed and should never be tightened or removed.
¡When installing fuel lines to the valve, be sure to check for fuel leakage.
¡A LEAKING VALVE MUST ALWAYS BE REPLACED.
NOTE:
The fusible link valve is in the open position when the valve stem appears
above the center of the turn handle as shown in the illustration.
30
Laser 56 FUEL SYSTEM OPTIONS
EXTERNAL TANK INSTALLATION