Daikin DPSA Manual page 21

Rebel applied rooftop systems
Table of Contents

Advertisement

Table 2: Rebel Applied 031 – 052 Filter Information
Data
Panel Filters
Thickness (MERV)
Area (sqft)
Qty – Size
Pre Filters (for cartridge filters)
Thickness (MERV)
Area (sqft)
Qty – Size
Cartridge Filters
Thickness (MERV)
Area (sqft)
Qty – Size
Cartridge Final Filters
Thickness (MERV)
Area (sqft)
Qty – Size
Face Load Final Filters
Thickness (MERV)
Area (sqft)
Qty – Size
Large Wheel Filters
Thickness (MERV)
Area (sqft)
Qty - Size
Small Wheel with Bypass Filters
Thickness (MERV)
Area (sqft)
Qty – Size
www.DaikinApplied.com
31
35
40
2" (8), 4" (8), 4" (13)
42.67 ft²
(8) – 20" × 24", (4) – 24" × 24"
2" (8)
38.3 ft²
(9) – 20" × 24", (3) – 20" x 20"
4" (15), 12" (11,14, 16, Carbon)
38.3 ft²
(9) – 20" × 24", (3) – 20" × 20"
12" (14, 16)
35.6 ft²
(9) – 20" × 24", (2) – 20" × 20"
12" (16, HEPA)
34.0 ft²
(6) – 24" × 24", (5) - 12" × 24"
RA = 2" (8) / OA = 4" (8)
29.3 ft²
(4) – 20" × 24", (4) – 24" × 24"
RA = 2" (8) / OA = 4" (8)
29.3 ft²
(4) – 20" × 24", (4) – 24" × 24"
21
Physical Data
50
CAT 258 • REBEL APPLIED ROOFTOP
52

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dfsa