Using The Cooling Charging Charts; Cooling Charging Charts - Bryant Preferred 551J Service And Maintenance Instructions

Electric cooling/optional electric heat with puron (r-410a) refrigerant
Hide thumbs Also See for Preferred 551J:
Table of Contents

Advertisement

gage to the service port on the suction line. Mount the temperature
sensing device on the suction line and insulate it so the outdoor
ambient temperature does not affect the reading. Indoor-air cfm
must be within the normal operating range of the unit.
SIZE DESIGNATION
17
20
24
28

Using the Cooling Charging Charts

Take the outdoor coil leaving refrigerant temperature and read the
compressor discharge pressure gage. Refer to the chart to deter-
mine what the leaving temperature should be. If the leaving tem-
perature is high, add refrigerant.

COOLING CHARGING CHARTS

NOMINAL TON REFERENCE
15
17.5
20
25
Fig. 21 — Cooling Charging Chart - 15 Ton
If the leaving temperature is low, carefully recover some of the
charge. Recheck the compressor discharge pressure as the charge
is adjusted.
Select the appropriate unit charging chart from Fig. 21-24.
Note the outdoor coil leaving refrigerant temperature and read the
compressor discharge pressure gage. Refer to the chart to deter-
mine what the leaving temperature should be. If the leaving tem-
perature is high, add refrigerant. If the leaving temperature is low,
carefully recover some of the charge. Recheck the compressor dis-
charge pressure as the charge is adjusted.
For sizes 17-28, perform this procedure once for Circuit A and
once for Circuit B.
18

Advertisement

Table of Contents
loading

Table of Contents