Bryant Preferred 581J04-14 Service And Maintenance Instructions

Bryant Preferred 581J04-14 Service And Maintenance Instructions

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

Quick Links

Single Package Rooftop Gas Heat/Electric Cooling Unit
Service and Maintenance Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 2
UNIT ARRANGEMENT AND ACCESS . . . . . . . . . . . . . . 3
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Routine Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Seasonal Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
RETURN AIR FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Outside Air Hood. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Economizer Inlet Air Screen. . . . . . . . . . . . . . . . . . . . . . . . . 4
Manual Outside Air Hood Screen . . . . . . . . . . . . . . . . . . . . 4
SUPPLY FAN (BLOWER) SECTION . . . . . . . . . . . . . . . . 4
Supply Fan (Direct-Drive) . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Supply Fan (Belt-Drive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2-Speed Indoor Fan Motor System . . . . . . . . . . . . . . . . . . . 7
Identifying Factory Option . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
MOTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Replacing the Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Changing Fan Wheel Speed . . . . . . . . . . . . . . . . . . . . . . . . . 9
REMOTE VFD KEYPAD REFERENCE. . . . . . . . . . . . . . 9
COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Condenser Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
TXV Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Replacing TXV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant System Pressure Access Ports . . . . . . . . . . . . 14
Puron® (R-410A) REFRIGERANT . . . . . . . . . . . . . . . . . 15
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
COOLING CHARGING CHARTS. . . . . . . . . . . . . . . . . . 15
COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Replacing Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Compressor Rotation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Condenser-Fan Adjustment . . . . . . . . . . . . . . . . . . . . . . . . 18
CONVENIENCE OUTLETS . . . . . . . . . . . . . . . . . . . . . . . 20
SMOKE DETECTORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Smoke Detector Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Smoke Detector Locations . . . . . . . . . . . . . . . . . . . . . . . . . 22
Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53581019-01
with Puron
Printed in U.S.A.
Form SM581J-4-14-02
Preferred™ Series
581J04-14
®
(R-410A) Refrigerant
SENSOR AND CONTROLLER TESTS . . . . . . . . . . . . . 24
Sensor Alarm Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Controller Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dirty Controller Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dirty Sensor Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Dirty Sensor Test Procedure . . . . . . . . . . . . . . . . . . . . . . . 25
Changing the Dirt Sensor Test. . . . . . . . . . . . . . . . . . . . . . 25
Remote Station Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
SD-TRK4 Remote Alarm Test Procedure . . . . . . . . . . . . 25
Dirty Sensor Test Using an SD-TRK4. . . . . . . . . . . . . . . . 26
Detector Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . 27
Compressor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Relief Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Control Circuit, 24-V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
GAS HEATING SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . 28
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Fuel Types and Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Flue Gas Passageways. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Combustion-Air Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Burners and Igniters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Removing the Heat Exchanger. . . . . . . . . . . . . . . . . . . . . . 31
Burner Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Orifice Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Troubleshooting Heating System. . . . . . . . . . . . . . . . . . . . 41
RTU Open Control System . . . . . . . . . . . . . . . . . . . . . . . . 42
ECONOMIZER SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . 42
EconoMi$er IV Standard Sensors . . . . . . . . . . . . . . . . . . . 48
EconoMi$er IV Control Modes . . . . . . . . . . . . . . . . . . . . . 48
EconoMi$er IV Preparation. . . . . . . . . . . . . . . . . . . . . . . . 51
Differential Enthalpy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Single Enthalpy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
DCV Minimum and Maximum Position . . . . . . . . . . . . . . 52
Supply-Air Sensor Input. . . . . . . . . . . . . . . . . . . . . . . . . . . 52
EconoMi$er® X (Factory Option). . . . . . . . . . . . . . . . . . . 52
PRE-START-UP/START-UP . . . . . . . . . . . . . . . . . . . . . . 66
START-UP, GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Additional Installation/Inspection . . . . . . . . . . . . . . . . . . . 66
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Outdoor-Air Inlet Screens . . . . . . . . . . . . . . . . . . . . . . . . . 67
Compressor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Refrigerant Service Ports . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Compressor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Pg 1
8-19
Replaces: SM581J-4-14-01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Preferred 581J04-14 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bryant Preferred 581J04-14

  • Page 1: Table Of Contents

    Preferred™ Series 581J04-14 Single Package Rooftop Gas Heat/Electric Cooling Unit ® with Puron (R-410A) Refrigerant Service and Maintenance Instructions CONTENTS FIOP Smoke Detector Wiring and Response ..23 SENSOR AND CONTROLLER TESTS ... . . 24 SAFETY CONSIDERATIONS .
  • Page 2: Safety Considerations

    Cooling......... .67 Main Burners .
  • Page 3: Unit Arrangement And Access

    UNIT ARRANGEMENT AND ACCESS AIR CONDITIONING • Condenser fan motor mounting bolts tightness General • Compressor mounting bolts Figures 1 and 2 show general unit arrangement and access • Condenser fan blade positioning locations. • Control box cleanliness and wiring condition FILTER ACCESS PANEL •...
  • Page 4: Outside Air Hood

    To re-install the access panel: To remove the screen, loosen the screws in the top retainer and slip the retainer up until the filter can be removed. Re-install by Slide the top of the panel up under the unit top panel. placing the frame in its track, rotating the retainer back down, Slide the bottom into the side channels.
  • Page 5 brushless design with a permanent magnet rotor. On the X13 Table 1 — Motor Tap Programing (Percent of ECM Motor design, the electronic circuitry is integral to the Full-Load Torque) motor assembly and cannot be serviced or replaced separately. 581J UNIT TAP 1 TAP 2 TAP 3...
  • Page 6: Supply Fan (Belt-Drive)

    TROUBLESHOOTING THE ECM MOTOR BLOWER PULLEY Troubleshooting the X13 ECM requires a voltmeter. Disconnect main power to the unit. V--- BELT Remove the motor power plug (including the control BRN lead) and VIO control signal lead at the motor terminals. MOTOR Restore main unit power.
  • Page 7: Staged Air Volume Control - 2 Speed Fan With Variable Frequency Drive (Vfd)

    Remove the belt by gently lifting the old belt over one of Set movable flange at nearest keyway of pulley hub. the pulleys. Tighten setscrew and torque to 65 to 70 in.-lb (7.4 to Install the new belt by gently sliding the belt over both 7.9 Nm).
  • Page 8: Unit Installation With 2-Speed Indoor Fan Motor System

    Table 3 — Model-Size / VFD Option Indicator POSITION IN MODEL VFD FIOP MODEL / SIZES NUMBER INDICATOR 581J / 07-14 G, J NOTE: See Appendix A for an example of Model Number Nomenclature. Unit Installation with 2-Speed Indoor Fan Motor Sys- tem Option 581J ROOFTOP Refer to the base unit installation instructions for standard re-...
  • Page 9: Changing Fan Wheel Speed

    24. Align the motor pulley and blower wheel pulley using a straight edge. See Fig. 10. CAUTION 25. Adjust the V-belt tension using adjustment tool. 26. Turn two jack bolts clockwise, moving the motor assembly EQUIPMENT DAMAGE HAZARD away from the blower pulley, increasing the V-belt tension. Failure to follow this CAUTION can result in premature 27.
  • Page 12: Cooling

    COOLING Avoid use of: • coil brighteners • acid cleaning prior to painting WARNING • high pressure washers • poor quality water for cleaning UNIT OPERATION AND SAFETY HAZARD Totaline environmentally sound coil cleaner is nonflammable, Failure to follow this warning could cause personal injury, hypoallergenic, non-bacterial, and a USDA accepted biode- death and/or equipment damage.
  • Page 13: Evaporator Coil

    TOTALINE ENVIRONMENTALLY SOUND COIL CLEANER APPLICATION INSTRUCTIONS Proper eye protection such as safety glasses is recom- mended during mixing and application. Remove all surface loaded fibers and dirt with a vacuum cleaner as described above. Thoroughly wet all finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins.
  • Page 14: Replacing Txv

    The suction pressure at the outlet of the evaporator coil is compressor. These are brass fittings with black plastic caps. transferred through the external equalizer tube to the The hose connection fittings are standard -in. SAE male underside of the diaphragm. flare couplings.
  • Page 15: Puron® (R-410A) Refrigerant

    Remove charge if below the curve Refrigerant Charge Amount of refrigerant charge is listed on the unit’s nameplate. Refer to Bryant GTAC2-5 Charging, Recovery, Recycling and Reclamation training manual and the following procedures. Unit panels must be in place when unit is operating during the charging procedure.
  • Page 16 2-Stage 6 Ton Charging Chart R-410A Refrigerant CHARGING CHART – R-410A REFRIGERANT (Cooling Mode - Compressor at Full Load COOLING MODE – OUTDOOR FAN MUST BE RUNNING and Outdoor Fans at High Speed) Add Charge if Above the Curve Add charge if above the curve Remove Charge if Below the Curve Remove charge if below the curve...
  • Page 17 CHARGING CHART – R-410A REFRIGERANT CHARGING CHART – R-410A REFRIGERANT COOLING MODE – ALL OUTDOOR FANS MUST BE RUNNING COOLING MODE – CIRCUIT A & B Add charge if above the curve Add charge if above the curve Remove charge if below the curve Remove charge if below the curve Compressor Discharge Pressure (psig) 48TM502682...
  • Page 18: Compressor

    COMPRESSOR Compressor Rotation Lubrication The compressor is charged with the correct amount of oil at the CAUTION factory. EQUIPMENT DAMAGE HAZARD Failure to follow this caution can result in premature wear CAUTION and damage to equipment. Scroll compressors can only compress refrigerant if rotat- UNIT DAMAGE HAZARD ing in the right direction.
  • Page 19 Fig. 31 — Typical Piping Schematic (Dual Circuit Unit Shown)
  • Page 20: Convenience Outlets

    CONVENIENCE OUTLETS Loosen the two screws at the GFCI duplex outlet, until approximately -in. (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing WARNING plate over the screw heads at the keyhole slots and align with the gasket;...
  • Page 21: Smoke Detectors

    SMOKE DETECTORS Smoke detectors are available as factory-installed options on 581J models. Smoke detectors may be specified for supply air only, for return air without or with economizer, or in combina- tion of supply air and return air. Return air smoke detectors are arranged for vertical return configurations only.
  • Page 22: Smoke Detector Locations

    Air is introduced to the duct smoke detector sensor’s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber.
  • Page 23: Completing Installation Of Return Air Smoke

    RETURN AIR SENSOR (Operating Position Shown) CONTROLLER MODULE SCREWS (2) RETURN AIR SAMPLING TUBE SAMPLE TUBE Fig. 39 — Return Air Sampling Tube Location (View reoriented to show opposite side for clarity) Fig. 41 — Return Air Sensor Operating Position Completing Installation of Return Air Smoke FIOP Smoke Detector Wiring and Response Detector...
  • Page 24: Sensor And Controller Tests

    Fig. 42 — Typical Smoke Detector System Wiring ADDITIONAL APPLICATION DATA Refer to Factory-Installed Smoke Detectors for Small and Me- IMPORTANT: OPERATIONAL TEST ALERT dium Rooftop Units 2 to 25 Tons for discussions on additional control features of these smoke detectors including multiple Failure to follow this ALERT can result in an unnecessary unit coordination.
  • Page 25: Dirty Sensor Test

    Dirty Sensor Test The dirty sensor test provides an indication of the sensor’s abil- IMPORTANT: OPERATIONAL TEST ALERT ity to compensate for gradual environmental changes. A sensor that can no longer compensate for environmental changes is Failure to follow this ALERT can result in an unnecessary considered 100% dirty and requires cleaning or replacing.
  • Page 26: Dirty Sensor Test Using An Sd-Trk4

    Indicators IMPORTANT: OPERATIONAL TEST ALERT NORMAL STATE The smoke detector operates in the normal state in the absence Failure to follow this ALERT can result in an unnecessary of any trouble conditions and when its sensing chamber is free evacuation of the facility. of smoke.
  • Page 27: Troubleshooting

    RESETTING ALARM AND TROUBLE CONDITION TRIPS PROTECTIVE DEVICES Manual reset is required to restore smoke detector systems to Compressor Protection Normal operation. For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an OVERCURRENT alarm or trouble condition. Check each sensor for Alarm or The compressor has internal line-break motor protection.
  • Page 28: Gas Heating System

    GAS HEATING SYSTEM Table 8 — Natural Gas Supply Line Pressure Ranges General UNIT UNIT The heat exchanger system consists of a gas valve feeding mul- MODEL SIZE tiple in-shot burners off a manifold. The burners fire into 581J 4.0 in. wg (996 Pa) 13.0 in.
  • Page 29: Flue Gas Passageways

    Flue Gas Passageways To inspect the flue collector box and upper areas of the heat exchanger: Remove the combustion blower wheel and motor assem- bly according to directions in Combustion-Air Blower sec- tion. See Fig. 50. Remove the flue cover to inspect the heat exchanger. Clean all surfaces as required using a wire brush.
  • Page 30: Burners And Igniters

    HEAT EXCHANGER SUPPORT RACK HEAT EXCHANGER COVER PANEL BURNER UNIT PARTITION CENTER PANEL POST Fig. 51 — Heat Exchanger Access - Internal Panels, Center Post, and HX Rack Locations Burners and Igniters ORIFICE CAUTION 1.00-in EQUIPMENT DAMAGE HAZARD (25.4 mm) Failure to follow this CAUTION can result in premature wear and damage to equipment.
  • Page 31: Removing The Heat Exchanger

    REMOVAL AND REPLACEMENT OF GAS TRAIN INTEGRATED GAS UNIT See Fig. 46, 49, and 53. RACEWAY CONTROLLER (IGC) Shut off manual gas valve. Shut off power to unit. Remove the control box access panel. Remove the control box high voltage cover. Remove the screw at the base of the burner partition panel (see Fig.
  • Page 32: Burner Ignition

    GAS VALVE Burner Ignition All three-phase models (except Low NOx) are equipped with Unit is equipped with a direct spark ignition 100% lockout sys- 2-stage gas valves. Single-phase models and all Low NOx tem. The Integrated Gas Unit Controller (IGC) is located in the models are equipped with single-stage gas valves.
  • Page 33 LOW HEAT 72,000 BTUH INPUT AND 60,000 BTUH INPUT MEDIUM AND HIGH HEAT 115,000 BTUH INPUT, 150,000 BTUH INPUT, 90,000BTUH INPUT AND 120,000 BTUH INPUT Fig. 55 — Spark Adjustment (Size 04-07)
  • Page 34 125,000/90,000 BTUH INPUT 125,000/90,000 BTUH INPUT 180,000/120,000 BTUH INPUT 180,000/120,000 BTUH INPUT 240,000/180,000 BTUH INPUT 240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUT 250,000/200,000 BTUH INPUT Fig. 57 — Spark Adjustment (Size 12) Fig. 56 — Spark Adjustment (Size 08-09)
  • Page 35 IGNITER AND SENSOR LOCATIONS (BRACKET HEAT COVER NOT SHOWN FOR CLARITY) 0.130 5 CELL 50TM400735 6 CELL 50TM400484 0.181 8 CELL 50TM400485 10 CELL 50TM400439 Fig. 58 — Spark Adjustment (Size 14) REGULATOR COVER SCREW (2) REGULATOR ON/OFF COVER SCREW PLASTIC ADJUST ON/OFF SWITCH...
  • Page 36 RED LED - STATUS Fig. 60 — Integrated Gas Control (IGC) Board...
  • Page 37 Table 13 — IGC Connections TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O CONNECTION PIN NUMBER INPUTS Input power from TRAN 1 control box 24 VAC — RT, C Speed sensor gas section analog input J1, 1-3 Flame sensor gas section switch input —...
  • Page 38 Table 15 — Altitude Compensation* (Sizes 04-06) NATURAL GAS NOMINAL HEAT INPUT ELEVATION 72K BTUH 115KBTUH 150K BTUH Feet Meters Orifice Size Input (btu/hr) Orifice Size Input (btu/hr) Orifice Size Input (btu/hr) 0 to 2,000 0-610 72,000 115,000 †30 150,000 2,000 66,240 105,800...
  • Page 39 Table 16 — Altitude Compensation* (Sizes 07-12) NATURAL GAS NOMINAL HEAT INPUT ELEVATION 72K BTUH 125K BTUH 150K BTUH 180K BTUH 224K BTUH 250K BTUH Orifice Input Orifice Input Orifice Input Orifice Input Orifice Input Orifice Input Size (btu/hr) Size (btu/hr) Size (btu/hr)
  • Page 40 Table 17 — Altitude Compensation* (Size 14) NATURAL GAS NOMINAL HEAT INPUT ELEVATION 150K BTUH 180K BTUH 240K BTUH 315K BTUH 380K BTUH ORIFICE INPUT ORIFICE INPUT ORIFICE INPUT ORIFICE INPUT ORIFICE INPUT SIZE (BTU/HR) SIZE (BTU/HR) SIZE (BTU/HR) SIZE (BTU/HR) SIZE (BTU/HR)
  • Page 41: Troubleshooting Heating System

    MINIMUM HEATING ENTERING AIR TEMPERATURE Thermostat When operating on first stage heating, the minimum tempera- ture of air entering the dimpled heat exchanger is 50°F continu- ous and 45°F intermittent for standard heat exchangers and 40°F continuous and 35°F intermittent for stainless steel heat OALT exchangers.
  • Page 42: Rtu Open Control System

    Table 20 — IGC Board LED Alarm Codes ACTION TAKEN BY FLASH DESCRIPTION RESET METHOD PROBABLE CAUSE CONTROL CODE Normal Operation — — — Loss of power to the IGC. Check 5 amp fuse Hardware Failure No gas heating. — on IGC, power to unit, 24V circuit breaker, transformer, and wiring to the IGC.
  • Page 43 OUTSIDE AIR OUTSIDE AIR TEMPERATURE SENSOR TEMPERATURE SENSOR LOW AMBIENT ECONOMI$ER2 PLUG ECONOMI$ER IV SENSOR CONTROLLER (W7212) Fig. 64 — EconoMi$er2 Component Locations Fig. 63 — EconoMi$er X Component Locations...
  • Page 44 Fig. 65 — RTU Open Overlay for Economizer Wiring...
  • Page 45 Fig. 66 — VFD Overlay for W2770 Controller Wiring...
  • Page 46 FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK LEGEND NOTES: — Demand Controlled Ventilation 1. 620 ohm, 1 watt 5% resistor should be removed only when using — Indoor Air Quality differential enthalpy or dry bulb. — Low Ambient Lockout Device 2.
  • Page 47 BLACK TRANSFORMER GROUND BLUE 500 OHM RESISTOR VIOLET PINK OAT SENSOR ACTULATOR FEEDBACK (2-10VDC) ORANGE ACTULATOR WHITE DIRECT DRIVE 4-20mA SIGNAL CONTROL ACTUATOR (4-20mA) ECONOMI$ER2 PLUG NOTES: 1. Switch on actuator must be in run position for economizer to operate. 3.
  • Page 48: Economi$Er Iv Standard Sensors

    EconoMi$er IV Standard Sensors OUTDOOR AIR LOCKOUT SENSOR Table 21 provides a summary of EconoMi$er IV logic. Trou- The EconoMi$er IV is equipped with an ambient temperature bleshooting instructions are enclosed. A functional view of the lockout switch located in the outdoor airstream which is used EconoMi$er IV control is shown in Fig.
  • Page 49 airstream is used for cooling. When using this mode of change- over control, turn the enthalpy set point potentiometer fully clockwise to the D setting. See Fig. 71. OUTDOOR ENTHALPY CHANGEOVER For enthalpy control, accessory enthalpy sensor (P/N: HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location.
  • Page 50 enthalpy to the return air enthalpy to determine EconoMi$er IV If a separate field-supplied transformer is used to power the use. The controller selects the lower enthalpy air (return or out- IAQ sensor, the sensor must not be grounded or the door) for cooling.
  • Page 51: Economi$Er Iv Preparation

    When the timeclock contacts are open (removing Use setting 1 or 2 for Bryant equipment. the 24-v signal from terminal N), the EconoMi$er IV control will be in unoccupied mode.
  • Page 52: Differential Enthalpy

    Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting. DCV Minimum and Maximum Position To check the DCV minimum and maximum position: Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.
  • Page 53 • Nominal Power Consumption (at 24 vac, 60 Hz) — 11.5 VA without sensors or actuators • Relay Digital Output Rating at 30 vac (maximum power from Class 2 input only) — 1.5A run: 3.5A inrush at 0.45PF (200,000 cycles) or 7.5A inrush at 0.45PF (100,000 cycles) •...
  • Page 54 ECONOMIZER MODULE WIRING DETAILS Table 24 — Economizer Module Use Fig. 79 and Tables 23 and 24 to locate the wiring terminals (Right Hand Terminal Blocks) for the Economizer module. NOTE: The four terminal blocks are removable. Slide out each LABEL TYPE DESCRIPTION...
  • Page 55 To use the keypad when working with menus: Table 25 — HH57AC081 Sensor Wiring Terminations • Press the ▲ (Up arrow) button to move to the previous menu. TERMINAL TYPE DESCRIPTION • Press the ▼ (Down arrow) button to move to the next NUMBER LABEL menu.
  • Page 56 located after the cooling coil, in the fan section, where it is desig- The setup process uses a hierarchical menu structure that is nated as (Cooling) Supply Air Temperature or SAT sensor. easy to use. Press the ▲ and ▼ arrow buttons to move forward and backward through the menus and press the button to select SETUP AND CONFIGURATION and confirm setup item changes.
  • Page 57 Table 27 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † Displays number of times actuator has cycled. ACT COUNT 1 to 65,535 1 cycle equals 180 degrees of actuator movement in any direction.
  • Page 58 Table 27 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † DCV MINIMUM DAMPER POSITION 2 to 10 vdc or 100 Displays only if a CO sensor is connected. Used for Va to 9990 cfm (ventilation min cfm) set point.
  • Page 59 Table 27 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † COOLING STAGE 3 DELAY 0 min, 5 min, 15 Delay after stage 2 cool has been active. Turns on second stage min, then 15 min of cooling when economizer is first stage call and mechanical STG3 DLY...
  • Page 60 Table 27 — W7220 Menu Structure* (cont) PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND Notes VALUE INCREMENT † RA SYLK T ERR RETURN AIR S-BUS SENSOR ERROR Return air enthalpy sensor has failed or become disconnected - RA SYLK H ERR check wiring, then replace sensor if the alarm continues.
  • Page 61 Table 28 — Damper Minimum Position Settings and Readings on Checkout Menu DEMAND CONTROLLED VENTILATION FAN SPEED SETPOINTS CHECKOUT SENSOR) MIN POS VMAX–HS MIN POS H VMAX–HS MIN POS L VMAX–LS VENT MIN VMAX–HS VENT MAX VMAX–HS VENT MIN H VMAX–HS VENT MAX H VMAX–LS...
  • Page 62 Table 31 — Enthalpy Operation without DCV (CO Sensor) — 1 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I FAN SPEED Y1-O Y2-O OCCUPIED UNOCCUPIED VENTILATION (DCV) ECONOMIZE High 0-v/Off 0-v/Off MIN POS Closed High 24-v/On 0-v/Off MIN POS Closed High 24-v/On...
  • Page 63 Table 34 — Dry Bulb Operation with DCV (CO Sensor) — 2 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I Y1-O Y2-O OCCUPIED UNOCCUPIED SPEED VENTILATION (DCV) ECONOMIZE 0v/Off 0v/Off VENTMIN Closed 24v/On 0v/Off VENTMIN Closed HIGH 24v/On 24v/On VENTMIN Closed...
  • Page 64 Table 36 — Enthalpy Operation with DCV (CO Sensor) — 2 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I Y1-O Y2-O OCCUPIED UNOCCUPIED SPEED VENTILATION (DCV) ECONOMIZE 0v/Off 0v/Off VENTMIN Closed 24v/On 0v/Off VENTMIN Closed HIGH 24v/On 24v/On VENTMIN Closed 0v/Off...
  • Page 65 ECONOMIZING DUAL ENTHALPY AVAILABLE HIGH LIMIT NOT AVAILABLE SINGLE ENTHALPY P2 (T,RH) (T,RH) TEMPERATURE Fig. 83 — Single Enthalpy Curve Boundaries Table 38 — Single Enthalpy and Dual Enthalpy High Limit Curves POINT P1 POINT P2 ENTHALPY TEMP. DRY TEMP. ENTHALPY HUMIDITY HUMIDITY...
  • Page 66: Pre-Start-Up/Start-Up

    You can also navigate to the Alarms menu at any time. Proceed as follows to inspect and prepare the unit for initial start-up: Clearing Alarms Remove all access panels. Once the alarm has been identified and the cause has been re- Read and follow instructions on all WARNING, CAU- moved (e.g.
  • Page 67: Return-Air Filters

    Return-Air Filters Ensure correct filters are installed in unit (see Appendix B — WARNING Physical Data). Do not operate unit without return-air filters. FIRE, EXPLOSION HAZARD Outdoor-Air Inlet Screens Failure to follow this warning could result in death, serious Outdoor-air inlet screen must be in place before operating unit. personal injury and/or property damage.
  • Page 68 Heating To restore the original default value, reset the power to the unit. To shut off unit, set system selector switch at OFF position. Purge gas supply line of air by opening union ahead of the Resetting heating selector lever below room temperature will gas valve.
  • Page 69 APPENDIX A — MODEL NUMBER NOMENCLATURE 13 14 Unit Type Packaging and 2-Speed Indoor Fan High Efficiency Motor Gas Heat RTU A = Standard Packaging, electro mech. controls that require W7212 EconoMi$er IV B = LTL Packaging, electro mech. controls that Model require W7212 EconoMi$er IV J –...
  • Page 70 APPENDIX B — PHYSICAL DATA Table A — PHYSICAL DATA (Cooling) 3 to 5 Tons 581J*04A/B/C 581J*04G/H/J 581J*05A/B/C 581J*05G/H/J 581J*06A/B/C 581J*06G/H/J Refrigeration System # Circuits / # Comp. / Type 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll...
  • Page 71 APPENDIX B — PHYSICAL DATA Table A — PHYSICAL DATA (Cooling) 3 to 5 Tons (cont) 581J*04A/B/C 581J*04G/H/J 581J*05A/B/C 581J*05G/H/J 581J*06A/B/C 581J*06G/H/J Cond. fan / motor Qty / Motor Drive Type 1 / direct 1 / direct 1 / direct 1 / direct 1 / direct 1 / direct...
  • Page 72 APPENDIX B — PHYSICAL DATA Table B — PHYSICAL DATA (Cooling) 6 Tons 581J*07A/B/C 581J*07G/H/J 581J*07D/F 581*07K/M Refrigeration System # Circuits / # Comp. / Type 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / 2-Stage Scroll 1 / 1 /2-Stage Scroll Puron refrigerant (R-410A) charge (lb-oz)
  • Page 73 APPENDIX B — PHYSICAL DATA Table B — PHYSICAL DATA (Cooling) 6 Tons (cont) 581J*07A/B/C 581J*07G/H/J 581J*07D/F 581*07K/M Cond. fan / motor Qty / Motor Drive Type 2 / direct 2 / direct 2 / direct 2 / direct Motor HP / RPM / 1100 / 1100 / 1100...
  • Page 74 APPENDIX B — PHYSICAL DATA Table C — PHYSICAL DATA (Cooling) 7.5 to 8.5 Tons 581J*08D/F 581*08K/M 581J*09D/F 581*09K/M Refrigeration System # Circuits / # Comp. / Type 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll RTPF models R-410A charge A/B (lbs - oz) 9 - 10 / 9 - 10 —...
  • Page 75 APPENDIX B — PHYSICAL DATA Table D — PHYSICAL DATA (Cooling) 10 to 12.5 Tons 581J*11D/F 581*11K/M 581J*12D/F 581*12K/M 581J*14D/F 581*14K/M Refrigeration System # Circuits / # Comp. / Type 2/2/Scroll 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll...
  • Page 76 APPENDIX C — FAN PERFORMANCE Table E — 581J*04 Horizontal Unit - Direct Drive Table F — 581J*04 Vertical Unit - Direct Drive Fan Fan Performance Performance SPEED SPEED (TORQUE) (TORQUE) 0.45 0.23 0.30 0.19 0.33 0.22 0.17 0.17 1050 0.22 0.20 1050...
  • Page 77 APPENDIX C — FAN PERFORMANCE Table G — 581J*05 Horizontal Unit - Direct Drive Table H — 581J*05 Vertical Unit - Direct Drive Fan Performance Fan Performance SPEED SPEED (TORQUE) (TORQUE) 1200 0.49 0.35 1200 0.38 0.30 1300 0.34 0.33 1300 0.24 0.28...
  • Page 78 APPENDIX C — FAN PERFORMANCE Table I — 581J*06 Horizontal Unit - Direct Drive Table J — 581J*06 Vertical Unit - Direct Drive Fan Fan Performance Performance SPEED SPEED (TORQUE) (TORQUE) 1500 0.40 0.50 1500 0.27 0.45 1625 0.20 0.48 1625 0.08 0.43...
  • Page 79 APPENDIX C — FAN PERFORMANCE Table K — 581J*04 3 Phase without Perfect Humidity™ 3 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.14 0.24 0.35 0.48 1007 0.63 0.16 0.26 0.38 0.51 1023 0.66 1050 0.18...
  • Page 80 APPENDIX C — FAN PERFORMANCE Table M — 581J*04 3 Phase with Perfect Humidity™ 3 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.14 0.24 0.35 0.48 1007 0.63 0.16 0.26 0.38 0.51 1023 0.66 1050 0.18...
  • Page 81 APPENDIX C — FAN PERFORMANCE Table O — 581J*04 1 Phase with Perfect Humidity™ 3 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.14 0.24 0.35 0.48 1007 0.63 0.16 0.26 0.38 0.51 1023 0.66 1050 0.18...
  • Page 82 APPENDIX C — FAN PERFORMANCE Table Q — 581J*05 3 Phase without Perfect Humidity™ 4 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1200 0.24 0.35 0.48 0.63 1074 0.78 1300 0.29 0.41 0.54 1019 0.69 1099...
  • Page 83 APPENDIX C — FAN PERFORMANCE Table S — 581J*05 3 Phase with Perfect Humidity™ 4 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1200 0.24 0.35 0.48 0.63 1074 0.78 1300 0.29 0.41 0.54 1019 0.69 1099...
  • Page 84 APPENDIX C — FAN PERFORMANCE Table U — 581J*05 1 Phase with Perfect Humidity™ 4 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1200 0.24 0.35 0.48 0.63 1074 0.78 1300 0.29 0.41 0.54 1019 0.69 1099...
  • Page 85 APPENDIX C — FAN PERFORMANCE Table W — 581J*06 3 Phase without Perfect Humidity™ 5 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1500 0.41 0.55 1002 0.71 1088 0.87 1167 1.05 1625 0.50 0.65 1041 0.81...
  • Page 86 APPENDIX C — FAN PERFORMANCE Table Y — 581J*06 3 Phase with Perfect Humidity™ 5 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1500 0.41 0.55 1002 0.71 1088 0.87 1167 1.05 1625 0.50 0.65 1041 0.81...
  • Page 87 APPENDIX C — FAN PERFORMANCE Table AA — 581J*06 1 Phase with Perfect Humidity™ 5 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1500 0.41 0.55 1002 0.71 1088 0.87 1167 1.05 1625 0.50 0.65 1041 0.81...
  • Page 88 APPENDIX C — FAN PERFORMANCE Table AC — 581J*07 3 Phase 6 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1800 0.33 0.51 0.72 0.96 1.23 1950 0.38 0.58 0.80 1.04 1.31 2100 0.45 0.65 0.88 1.13...
  • Page 89 APPENDIX C — FAN PERFORMANCE Table AE — 581J*08 3 Phase 7.5 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2250 0.36 0.51 0.66 0.82 0.98 2438 0.43 0.59 0.75 0.92 1.09 2625 0.51 0.68 0.85 1.03...
  • Page 90 APPENDIX C — FAN PERFORMANCE Table AG — 581J*09 3 Phase 8.5 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2550 0.47 0.64 0.81 0.99 1.16 2750 0.57 0.75 0.93 1.11 1.30 3000 0.70 0.89 1.09 1.29...
  • Page 91 APPENDIX C — FAN PERFORMANCE Table AI — 581J*11 3 Phase 10 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3000 0.70 0.89 1.09 1.29 1.50 3250 0.85 1.06 1.27 1.49 1.71 3500 1.03 1.25 1.48 1.71...
  • Page 92 APPENDIX C — FAN PERFORMANCE Table AK — 581J*12 3 Phase 10 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3000 0.70 0.89 1.09 1.29 1.50 3250 0.85 1.06 1.27 1.49 1.71 3500 1.03 1.25 1.48 1.71...
  • Page 93 APPENDIX C — FAN PERFORMANCE Table AM — 581J*14 3 Phase 12.5 Ton Horizontal Supply — Belt Drive Fan Performance AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3438 0.57 0.78 1.02 1.30 1.62 3750 0.69 0.91 1.17 1.45 1.77 4063 0.84 1.07 1.33 1.62...
  • Page 94 Bryant recommends the lower horsepower option. For information on the electrical properties of Bryant motors, please see the Electrical Data section of this unit’s product data. For more information on the performance limits of Bryant motors, see the application data section of this unit’s product data.
  • Page 95 APPENDIX D — WIRING DIAGRAMS Table AO — Wiring Diagrams 48HC*A04-D14 UNITS STANDARD PERFECT HUMIDITY™ SIZE VOLTAGE CONTROL POWER CONTROL POWER 230-1-60 48TM502526 (page 103) 48TM503099 (Page 126) 208/230-3-60 48TM502527 (page 104) 48TM503100 (Page 127) 04 - 06 48TM502525 (page 96) 48TM503098 (Page 121) 460-3-60 48TM502527 (page 104)
  • Page 96 APPENDIX D — WIRING DIAGRAMS Fig. B — 581J*04-06 YAC Control Diagram — 208-1-60; 208/230-3-60; 460/575-3-60...
  • Page 97 APPENDIX D — WIRING DIAGRAMS Fig. C — 581J*07D/F YAC Control Diagram — 208/230-3-60; 460/575-3-60 (6 Ton 2 Stage Cooling)
  • Page 98 APPENDIX D — WIRING DIAGRAMS Fig. D — 581J*07D/F YAC Control Diagram — 208/230-3-60; 460/575-3-60 (6 Ton 2 Stage with Dehumidification)
  • Page 99 APPENDIX D — WIRING DIAGRAMS Fig. E — 581J*07A/B/C YAC Control Diagram — 208/230-3-60; 460/575-3-60...
  • Page 100 APPENDIX D — WIRING DIAGRAMS Fig. F — 581J*08-09 YAC Control Diagram — 208/230-3-60; 460/575-3-60...
  • Page 101 APPENDIX D — WIRING DIAGRAMS Fig. G — 581J*11YAC Control Diagram — 208/230-3-60, 460/575-3-60...
  • Page 102 APPENDIX D — WIRING DIAGRAMS Fig. H — 581J*12 YAC Control Diagram — 208/230-3-60; 460/575-3-60...
  • Page 103 APPENDIX D — WIRING DIAGRAMS Fig. I — 581J*04-06 YAC Power Diagram — 208/230-1-60...
  • Page 104 APPENDIX D — WIRING DIAGRAMS Fig. J — 581J*04-06 YAC Power Diagram — 208/230-3-60; 460-3-60...
  • Page 105 APPENDIX D — WIRING DIAGRAMS Fig. K — 581J*04-06 YAC Power Diagram — 575-3-60...
  • Page 106 APPENDIX D — WIRING DIAGRAMS Fig. L — 581J*07-12D/F YAC Power Diagram — 208/230-3-60, 460-3-60 (6 Ton 2 Stage with Cooling)
  • Page 107 APPENDIX D — WIRING DIAGRAMS Fig. M — 581J*07-12D/F YAC Power Diagram — 208/230-3-60, 460-3-60 (6 Ton 2 Stage with Dehumidification)
  • Page 108 APPENDIX D — WIRING DIAGRAMS Fig. N — 581J*07-12A/B/C YAC Power Diagram — 208/230-3-60, 460-3-60...
  • Page 109 APPENDIX D — WIRING DIAGRAMS Fig. O — 581J*07-12A/B/C YAC Power Diagram — 575-3-60...
  • Page 110 APPENDIX D — WIRING DIAGRAMS Fig. P — 581J*08-09 YAC Power Diagram — 230/460-3-60...
  • Page 111 APPENDIX D — WIRING DIAGRAMS Fig. Q — 581J*08-09 YAC Power Diagram — 575-3-60...
  • Page 112 APPENDIX D — WIRING DIAGRAMS Fig. R — 581J*11 YAC Power Diagram 208/230-3-60...
  • Page 113 APPENDIX D — WIRING DIAGRAMS Fig. S — 581J*11 YAC Power Diagram 460-3-60...
  • Page 114 APPENDIX D — WIRING DIAGRAMS Fig. T — 581J*11 YAC Power Diagram 575-3-60...
  • Page 115 APPENDIX D — WIRING DIAGRAMS Fig. U — 581J*12 YAC Power Diagram — 230/460-3-60...
  • Page 116 APPENDIX D — WIRING DIAGRAMS Fig. V — 581J*12 YAC Power Diagram — 575-3-60...
  • Page 117 APPENDIX D — WIRING DIAGRAMS Fig. W — 581J*14 YAC Control Diagram — 208/230-3-60; 460/575-3-60...
  • Page 118 APPENDIX D — WIRING DIAGRAMS Fig. X — 581J*14 YAC Power Diagram — 208/230-3-60...
  • Page 119 APPENDIX D — WIRING DIAGRAMS Fig. Y — 581J*14 YAC Power Diagram — 460-3-60...
  • Page 120 APPENDIX D — WIRING DIAGRAMS Fig. Z — 581J*14 YAC Power Diagram — 575-3-60...
  • Page 121 APPENDIX D — WIRING DIAGRAMS Fig. AA — 581J*04-06 YAC Control Diagram — 230-1-60; 230/460/575-3-60 with Dehumidification...
  • Page 122 APPENDIX D — WIRING DIAGRAMS Fig. AB — 581J*07A/B/C YAC Control Diagram — 230-1-60; 230/460/575-3-60 with Dehumidification...
  • Page 123 APPENDIX D — WIRING DIAGRAMS Fig. AC — 581J*08-09 YAC Control Diagram — 230/460/575-3-60 with Dehumidification...
  • Page 124 APPENDIX D — WIRING DIAGRAMS Fig. AD — 581J*11 YAC Control Diagram — 230-1-60; 230/460/575-3-60 with Dehumidification...
  • Page 125 APPENDIX D — WIRING DIAGRAMS Fig. AE — 581J*12 YAC Control Diagram — 230/460/575-3-60 with Dehumidification...
  • Page 126 APPENDIX D — WIRING DIAGRAMS Fig. AF — 581J*04-06 YAC Power Diagram — 208/230-1-60 with Perfect Humidity™ System...
  • Page 127 APPENDIX D — WIRING DIAGRAMS Fig. AG — 581J*04-06 YAC Power Diagram — 230/460-3-60 with Perfect Humidity™ System...
  • Page 128 APPENDIX D — WIRING DIAGRAMS Fig. AH — 581J*04-06 YAC Power Diagram — 575-3-60 with Perfect Humidity™ System...
  • Page 129 APPENDIX D — WIRING DIAGRAMS Fig. AI — 581J*07A/B/C YAC Power Diagram — 230/460-3-60 with Perfect Humidity™ System...
  • Page 130 APPENDIX D — WIRING DIAGRAMS Fig. AJ — 581J*07A/B/C YAC Power Diagram — 575-3-60 with Perfect Humidity™ System...
  • Page 131 APPENDIX D — WIRING DIAGRAMS Fig. AK — 581J*08-09 YAC Power Diagram — 230/460-3-60 with Perfect Humidity™ System...
  • Page 132 APPENDIX D — WIRING DIAGRAMS Fig. AL — 581J*08-09 YAC Power Diagram — 575-3-60 with Perfect Humidity™ System...
  • Page 133 APPENDIX D — WIRING DIAGRAMS Fig. AM — 581J*11 YAC Power Diagram — 208/230-3-60 with Perfect Humidity™ System...
  • Page 134 APPENDIX D — WIRING DIAGRAMS Fig. AN — 581J*11 YAC Power Diagram — 460-3-60 with Perfect Humidity™ System...
  • Page 135 APPENDIX D — WIRING DIAGRAMS Fig. AO — 581J*11 YAC Power Diagram — 575-3-60 with Perfect Humidity™ System...
  • Page 136 APPENDIX D — WIRING DIAGRAMS Fig. AP — 581J*12 YAC Power Diagram — 230/460-3-60 with Perfect Humidity™ System...
  • Page 137 APPENDIX D — WIRING DIAGRAMS Fig. AQ — 581J*12 YAC Power Diagram — 575-3-60 with Perfect Humidity™ System...
  • Page 138 APPENDIX D — WIRING DIAGRAMS Fig. AR — 581J*14 YAC Control Diagram — 230/460/575-3-60 with Perfect Humidity™ System...
  • Page 139 APPENDIX D — WIRING DIAGRAMS Fig. AS — 581J*14 YAC Power Diagram — 208/230-3-60 with Perfect Humidity™ System...
  • Page 140 APPENDIX D — WIRING DIAGRAMS Fig. AT — 581J*14 YAC Power Diagram — 460-3-60 with Perfect Humidity™ System...
  • Page 141 APPENDIX D — WIRING DIAGRAMS Fig. AU — 581J*14 YAC Power Diagram — 575-3-60 with Perfect Humidity™ System...
  • Page 142 APPENDIX D — WIRING DIAGRAMS 50HE500891 Fig. AV — YAC Direct Digital System Control Wiring Diagram System...
  • Page 143 APPENDIX D — WIRING DIAGRAMS Fig. AW — RTU-Open Wiring Diagram...
  • Page 144 APPENDIX E — MOTORMASTER SENSOR LOCATIONS Fig. AZ — 581J*07 Outdoor Circuiting Fig. AX — 581J*04 Outdoor Circuiting Fig. BA — 581J*08A/B/C Outdoor Circuiting Fig. AY — 581J*05/06 Outdoor Circuiting...
  • Page 145 APPENDIX E — MOTORMASTER SENSOR LOCATIONS SENSOR LOCATION TIE WRAP 9.0” C12492 ® Fig. BD — 581J*08D/F Motormaster Sensor Fig. BB — 581J*09A/B/C Outdoor Circuiting Location — Novation ® Coils (MCHX) SENSOR SENSOR LOCATION LOCATION SENSOR LOCATION TIE WRAP CIRCUIT A CIRCUIT B Fig.
  • Page 146 Copyright 2019 Bryant Heating & Cooling Systems Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53581019-01 Printed in U.S.A. Form SM581J-4-14-02 Pg 146 8-19 Replaces: SM581J-4-14-01...
  • Page 147 UNIT START-UP CHECKLIST (Remove and use for Job File) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sec- tions of this Service and Maintenance Instructions document.
  • Page 148 9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized (Y/N) _____ 10. Restore set-points for thermostat and humidistat (Y/N) _____ REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS. Copyright 2019 Bryant Heating & Cooling Systems Cat. No. 04-53581019-01 Edition Date: 8-19 Printed in U.S.A.

Table of Contents