C.10 EM-EA1 settings
0 - default > no function, for additional options, please refer to the manual (refer to the
commissioning section in the installation manual), press OK to confirm the setting
C.11 Date
to adjust the date > day, month, year, press OK to confirm each setting
press
C.12 Time
press
to adjust the time > hours, minutes, press OK to confirm each setting
C.13 Summer/ Winter Time changeover
ON > time will be changed automatically OFF - default > constant time,
press OK to confirm the setting
C.14 Plug 96 additional options
For additional options, please refer to the commissioning section in the installation manual.
Note: This step does not need to be adjusted for switch live activation.
C.15 Vitotrol 200-E
Only when C.7 is set to 4 (weather comp.) select ON to activate Vitotrol 200-E,
press OK to confirm the setting
End
After completing the last step the arrow will appear indicating commissioning is complete
press OK to confirm the setting and start the flue gas sensor check. The boiler will restart.
FST
will appear (the boiler is carrying out flue gas sensor check & will fire for a few seconds
to raise sensor temperature). Please wait for this to complete. Once completed the boiler set
temperature will appear on the screen and boiler is ready to run.