Riello RG4S TL Installation, Use And Maintenance Instructions page 39

Light oil burners
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 35
3.3 HYDRAULIC SYSTEMS
WARNING:
The pump is designed to allow working with two pipes.
In order to obtain one pipe working it is necessary to unscrew the
pin (2), remove the by-pass screw (3) and then screw again the pin
(2), (see fig. 8).
It is necessary to install a filter on the fuel supply line.
Before starting the burner make sure that the return pipe-line is not
clogged. An excessive back pressure would cause the damage of
the pump seal.
*
D5338
PRIMING PUMP:
On the system in fig. 7 it is sufficient to loosen the suction gauge
connection (6, fig. 8) and wait until oil flows out.
On the systems in fig. 9 and 10 start the burner and wait for the priming.
Should lock-out occur prior to the arrival of the fuel, await at least 20 seconds
before repeating the operation.
The pump suction should not exceed a maximum of 0.4 bar (30 cm Hg).
Beyond this limit gas is released from the oil. Oil pipes must be completely tight.
In the vacuum systems (fig. 10) the return line should terminate within the oil tank
at the same level as the suction line. In this case a non-return valve is not re-
quired. Should however the return line arrive over the fuel level, a non-return
valve is required.
This solution however is less safe than previous one, due to the possibility of
leakage of the valve.
*
ONLY FOR ITALY : Automatic shut-off device as per Ministry of Internal Affairs' regulation no. 73 dated 7/29/71.
*
H = difference of level;
1916
H
Fig. 7
meters
0.5
1
1.5
2
Fig. 9
L = max. length of the suction line;
D5527
L meters
I. D.
I. D.
8 mm
10 mm
10
20
20
40
40
80
60
100
I. D. = internal diameter of the oil pipes.
4
GB
1
Fig. 8
1 - Suction line
2 - Return line
3 - By-pass screw
4 - Gauge connection
5 - Pressure adjuster
6 - Suction gauge connection
7 - Valve
L meters
H
I. D.
meters
8 mm
0
35
0.5
30
1
25
1.5
20
2
15
3
8
3.5
6
Fig. 10
*
7
6
5
4
3
2
I. D.
10 mm
100
100
100
90
70
30
20
D5337

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rg4s396t1

Table of Contents