Enable
Disable
Intelligent refrig-
Enable only evaporation
53
erant control
temperature control
Enable only condensation
temperature control
54
Prohibited (Factory default)
On
Recovery operation
60
(*1)
Off
61
Prohibited (Factory default)
62
Prohibited (Factory default)
63
Prohibited (Factory default)
Setting number (x00)
Setting number (x01)
Electricity meter
······
No. setting 1 (*2)
70
Setting number (x98)
Setting number (x99)
Set the ones digit and tens digit of the No. of the electricity meter connected to
CN135.
Setting number (0xx)
Electricity meter
Setting number (1xx)
No. setting 2 (*2)
71
Setting number (2xx)
Set the hundreds digit of the No. of the electricity meter connected to CN135.
Setting number (xx00)
Setting number (xx01)
Electricity meter
pulse setting 1
(*3)
72
Setting number (xx98)
Setting number (xx99)
Set the ones digit and tens digit of the No. of the electricity meter pulse setting
connected to CN135.
Setting number (00xx)
Setting number (01xx)
Electricity meter
pulse setting 2
······
(*3)
73
Setting number (98xx)
Setting number (99xx)
Set the hundreds digit and thousands digit of the electricity meter pulse setting
connected to CN135.
*1: Do not set this for outdoor units with subordinate setting.
*2: When electricity meter No. is set to "000" and "201 to 299", the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to "0000", the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
(1) Turn on the power of the outdoor unit and enter standby mode.
When system is normal
POWER/MODE lamp lights up. (ERROR
lamp is off.)
ERROR lamp: OFF
POWER/MODE
lamp: ON
7 segment LED
indicator: OFF
MODE/EXIT
ENTER
button
button
SELECT button
En-17
0
0
0
1
5
3
0
2
0
3
5
4
0
0
0
0
6
0
0
1
6
1
0
0
6
2
0
0
6
3
0
0
0
0
0
1
7
0
···
···
9
8
9
9
0
0
7
1
0
1
0
2
0
0
0
1
7
2
9
8
9
9
0
0
0
1
7
3
···
···
9
8
9
9
When system is abnormal
Check the settings as there is an error in
the settings for outdoor unit address (DIP
switch SET3-1, 2) or number of connected
subordinate units (DIP switch SET3-3, 4).
ERROR lamp: Blinking
POWER/MODE
lamp: ON
7 segment LED
indicator: "-"
display
(2) Setting method
Use the "MODE/EXIT", "SELECT",
and "ENTER" buttons to configure
settings according to the proce-
dures below.
(If no setting is made, the factory
default setting will be displayed.)
1: Function setting
First 2 digits Last 2 digits
2: Setting the first
Every press of the
"SELECT" button will
change the setting
number for the first 2
digits.
EXIT: Press the "MODE/EXIT" button to cancel the setting mode.
: Press the "MODE/EXIT" button
: Press the "SELECT" button
: Press the "ENTER" button.
: Press the "ENTER" button for
more than 3 seconds.
7-segment LED display (LED 105, LED 104)
(When [F3] to [F9] are displayed, continue to press
the "SELECT" button until [F2] is displayed.)
(Flashing)
2 digits
3: Setting the last 2 digits
Continue to press the "SELECT" button until the
desired number appears at the last 2 digits.
Setting is complete when the lamp lights up
Press "ENTER" button to return to "2: Setting the
first 2 digits" (If there is no operation for 5 seconds
after the setting, the display will return to "2: Setting
the first 2 digits".)
(Continue to press the "SE-
LECT" button until the desired
number appears at the last 2
digits.)
Setting is complete when the lamp lights up
Press "ENTER" button to return to "2: Setting the
first 2 digits" (If there is no operation for 5 seconds
after the setting, the display will return to "2: Setting
the first 2 digits".)