M-LB-(Ex-)2000-System Surge Protection Barriers
Installation
3.3

Signal Loops Disconnection for Checking

During commissioning, you can disconnect the signal loops for the following checks.
Insulation check of the cable on the unprotected side
Check of the signal loops
Danger!
Explosion hazard from sparking when using operating elements on devices with equipment
protection level Gc
Using operating elements in a potentially explosive atmosphere can cause sparks
that can ignite the surrounding atmosphere.
Only use operating elements (e. g., switch, slider, button, etc.) in the absence of a potentially
explosive atmosphere.
Disconnecting the Signal Loops
Use a suitable screwdriver for disconnecting.
1.
Insert the screwdriver (4) into the groove (5) of the disconnect levers.
2.
To disconnect the unprotected side on terminal 3, lift disconnect lever 1 (3) until the lever
reaches its end position.
3.
To disconnect the protected side on terminal 2, lift disconnect lever 2 (2) until the lever reaches
its end position.
Figure 3.11
1
Device
2
Disconnect lever 2 for terminal 2
3
Disconnect lever 1 for terminal 3
4
Screwdriver
Groove
5
24
1
2
3
4
5