VDF650 User Manual
This parameter is used to determine the corresponding setting when the analog input
voltage is less than the minimum value. The unit's digit, ten's digit and hundred's digit of this
parameter respectively correspond to the setting for AI2, AI2 and AI3.
If the value of a certain digit is 0, when analog input voltage is less than the minimum input,
the corresponding setting of the minimum input (P4-14, P4-19, P4-24) is used.
If the value of a certain digit is 1, when analog input voltage is less than the minimum input,
the corresponding value of this analog input is 0.0%.
Function Code
P4-35
P4-36
P4-37
These parameters are used to set the delay time of the AC drive when the status of DI
terminals changes.
Currently, only DI1, DI2 and DI3 support the delay time function.
Function Code
P4-38
P4-39
Parameter Name
DI1 delay time
DI2 delay time
DI3 delay time
Parameter Name
DI valid mode
selection 1
DI valid mode
selection 2
Desc
Setting Range
0.0–3600.0s
0.0–3600.0s
0.0–3600.0s
Setting Range
Unit's digit (DI1 valid mode)
0: High level valid
1: Low level valid
Ten's digit (DI2 valid mode)
0, 1 (same as DI1)
Hundred's digit (DI3 valid mode)
0, 1 (same as DI1)
Thousand's digit (DI4 valid mode)
0, 1 (same as DI1)
Ten thousand's digit (DI5 valid mode)
0, 1 (same as DI1)
Unit's digit (DI6 valid mode)
0, 1 (same as DI1)
Ten's digit (DI7 valid mode)
0, 1 (same as DI1)
Hundred's digit (DI8 state)
0, 1 (same as DI1)
Thousand's digit (DI9 valid mode)
0, 1 (same as DI1)
Ten thousand's digit (DI10 valid
mode)
0, 1 (same as DI1)
- 171 -
r iption of Function Codes
Default
0.0s
0.0s
0.0s
Default
00000
00000