Mitsubishi FDK15KXZE1 Technical Manual page 84

Vrf inverter multi-system air-conditioners
Table of Contents

Advertisement

Error code
WAIT
Remote control:
1. Applicable model
All models
(In case that
is kept
WAIT
on displaying on the remote
control for more than 2 minutes
after power ON.)
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor unit control PCB anomaly
• Remote control anomaly
• Breakage of connecting wires
of remote control
• Outdoor unit control PCB
anomaly
Note:
(1) When anomaly occurs during establishing communication between indoor and outdoor unit, error code E5 is displayed (outdoor red LED
flash 2-times).
In case of E5, the way of troubleshooting is same as above mentioned (except for checking of connecting wire).
When reset the power after E5 occurs, if this anomaly recurs,
a short period (within 1 minute),
(2) If any error is detected 30 minutes after displaying "
LED
Green
Red
Keeps flashing Stays OFF
Indoor
Keeps flashing Keeps flashing
Outdoor
5. Troubleshooting
Diagnosis
is kept on
WAIT
displaying on the remote
control for more than 2
minutes after power ON.
(1)
Isn't
the power fuse (5A) on the
outdoor control PCB
blown?
NO
Note (1) Model FDC224, 280KXZPE1 only.
Is
AC380-415V detected at
the secondary side of
noise filter PCB terminal?
YES
Is
the connection of wire
between noise filter and
inverter PCBs OK?
YES
Does
indoor green LED keep
flashing?
YES
Does
indoor green LED flash
2 times?
YES
Are
the wires between indoor
and outdoor units
connected properly ?
YES
Is
AC380-415V detected
between L1-L2, L2-L3, L3-L1
respectively at outdoor
terminal block?
YES
Is
AC220-240V detected
between L-N at indoor
terminal block?
may be displayed. In such case, please wait for 3 minute after the power breaker OFF.
WAIT
WAIT
83
Content
WAIT
Once turn OFF the breaker
and turn ON it again at 3
minutes after power OFF.
Does it become normal?
NO
is displayed on remote control. If power ON/OFF is repeated in
WAIT
" on the remote control, the display changes to "INSPECT I/U".
'17 • KX-T-264
(1)
Countermeasure
Replace fuse
YES
(Refer next page)
Replace noise filter PCB.
NO
Connect wires correctly.
NO
Indoor unit control PCB
NO
anomaly  Replace it.
Indoor/outdoor unit control
PCB anomaly  Replace it.
Remote control anomaly
NO
 Replace it.
Breakage of wires for remote
control  Replace it.
Correct the connecting wires
NO
between indoor and outdoor
units.
Outdoor unit control PCB
NO
anomaly  Replace it.
Breakage of connecting wire
NO
Noise.
Indoor unit control PCB
YES
anomaly  Replace it.