Cooling Information; Ccn/Linkage Display Table; Compressor Run Hours Display Table; Compressor Starts Display Table - United Technologies Carrier Weathermaker 48A2 Controls, Start-Up, Operation, Service, And Troubleshooting

Single package large rooftop units with comfortlink version 8.x controls
Table of Contents

Advertisement

ITEM
COOL

COOLING INFORMATION

C.CAP
Current Running Capacity
CUR.S
Current Cool Stage
REQ.S
Requested Cool Stage
MAX.S
Maximum Cool Stages
DEM.L
Active Demand Limit
SUMZ
COOL CAP. STAGE CONTROL
SMZ
Capacity Load Factor
ADD.R
Next Stage EDT Decrease
SUB.R
Next Stage EDT Increase
R.PCT
Rise Per Percent Capacity
Y.MIN
Cap Deadband Subtracting
Y.PLU
Cap Deadband Adding
Z.MIN
Cap Threshold Subtracting
Z.PLU
Cap Threshold Adding
H.TMP
High Temp Cap Override
L.TMP
Low Temp Cap Override
PULL
Pull Down Cap Override
SLOW
Slow Change Cap Override
HMZR
HUMIDIMIZER
CAPC
Humidimizer Capacity
C.EXV
Condenser EXV Position
B.EXV
Bypass EXV Position
RHV
Humidimizer 3-Way Valve
C.CPT
Cooling Control Point
EDT
Evaporator Discharge Tmp
H.CPT
Heating Control Point
LAT
Leaving Air Temperature
ITEM
TRIP
MODE TRIP HELPER
UN.C.S
Unoccup. Cool Mode Start
UN.C.E
Unoccup. Cool Mode End
OC.C.S
Occupied Cool Mode Start
OC.C.E
Occupied Cool Mode End
TEMP
Ctl.Temp RAT,SPT or Zone
OC.H.E
Occupied Heat Mode End
OC.H.S
Occupied Heat Mode Start
UN.H.E
Unoccup. Heat Mode End
UN.H.S
Unoccup. Heat Mode Start
HVAC
ascii string spelling out the hvac modes
ITEM
LINK
CCN - LINKAGE
MODE
Linkage Active - CCN
L.Z.T
Linkage Zone Control Tmp
L.C.SP
Linkage Curr. Cool Setpt
L.H.SP
Linkage Curr. Heat Setpt
ITEM
HRS
COMPRESSOR RUN HOURS
HR.A1
Compressor A1 Run Hours
HR.A2
Compressor A2 Run Hours
HR.B1
Compressor B1 Run Hours
HR.B2
Compressor B2 Run Hours
ITEM
STRT
COMPRESSOR STARTS
ST.A1
Compressor A1 Starts
ST.A2
Compressor A2 Starts
ST.B1
Compressor B1 Starts
ST.B2
Compressor B2 Starts
Table 93 — Cooling Information Display Table
EXPANSION
Table 94 — Mode Trip Helper Display Table
EXPANSION
Table 95 — CCN/Linkage Display Table
EXPANSION
ON/OFF
Table 96 — Compressor Run Hours Display Table
EXPANSION
Table 97 — Compressor Starts Display Table
EXPANSION
RANGE
UNITS
%
%
–100  +100
^F
^F
RANGE
UNITS
UCCLSTRT
UCCL_END
OCCLSTRT
OCCL_END
CTRLTEMP
OCHT_END
OCHTSTRT
UCHT_END
UCHTSTRT
string
RANGE
UNITS
MODELINK
dF
LZT
dF
LCSP
dF
LHSP
RANGE
UNITS
0-999999
HRS
0-999999
HRS
0-999999
HRS
0-999999
HRS
RANGE
UNITS
0-999999
0-999999
0-999999
0-999999
94
POINT
WRITE STATUS
CAPTOTAL
COOL_STG
CL_STAGE
CLMAXSTG
DEM_LIM
forcible
SMZ
ADDRISE
SUBRISE
RISE_PCT
Y_MINUS
Y_PLUS
Z_MINUS
Z_PLUS
HI_TEMP
LOW_TEMP
PULLDOWN
SLO_CHNG
HMZRCAPC
COND_EXV
BYP_EXV
HUM3WVAL
COOLCPNT
EDT
HEATCPNT
LAT
POINT
WRITE STATUS
POINT
WRITE STATUS
POINT
WRITE STATUS
HR_A1
config
HR_A2
config
HR_B1
config
HR_B2
config
POINT
WRITE STATUS
CY_A1
config
CY_A2
config
CY_B1
config
CY_B2
config