ITEM
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type
CV.FN
Fan Mode (0=Auto, 1=Cont)
RM.CF
Remote Switch Config
CEM
CEM Module Installed
TCS.C
Temp.Cmp.Strt.Cool Factr
TCS.H
Temp.Cmp.Strt.Heat Factr
SFS.S
Fan Fail Shuts Down Unit
SFS.M
Fan Stat Monitoring Type
VAV.S
VAV Unocc.Fan Retry Time
SIZE
Unit Size (20-60)
DP.XR
Disch.Press. Transducers
SP.XR
Suct. Pres. Trans. Type
RFG.T
Refrig: 0=R22 1=R410A
CND.T
Cnd HX Typ:0=RTPF 1=MCHX
MAT.S
MAT Calc Config
MAT.R
Reset MAT Table Entries?
MAT.D
MAT Outside Air Default
ALTI
Altitude........in feet:
DLAY
Startup Delay Time
STAT
TSTAT_Both Heat and Cool
AUX.R
Auxiliary Relay Config
SENS
INPUT SENSOR CONFIG
SPT.S
Space Temp Sensor
SP.O.S
Space Temp Offset Sensor
SP.O.R
Space Temp Offset Range
RRH.S
Return Air RH Sensor
FLT.S
Filter Stat.Sw.Enabled ?
COOL
COOLING CONFIGURATION
Z.GN
Capacity Threshold Adjst
MC.LO
Compressor Lockout Temp
C.FOD
Fan-off Delay, Mech Cool
MLV
Min. Load Valve? (HGBP)
M.M.
Motor Master Control?
MM.OF
Motor Master Setpoint Offset
MM.RR
Motor Master PD Run Rate
MM.PG
Motor Master Proportional Gain
MM.DG
Motor Master Derivative Gain
MM.TI
Motor Master Integration Time
DS.EN
Enable Digital Scroll?
DS.MC
DS Min Digital Capacity
DS.AP
Dig Scroll Adjust Delta
DS.AD
Dig Scroll Adjust Delay
DS.RP
Dig Scroll Reduce Delta
DS.RD
Dig Scroll Reduce Delay
DS.RO
Dig Scroll Reduction OAT
DS.MO
Dig Scroll Max Only OAT
HPSP
Head Pressure Setpoint
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480166-01

CONTROLS SETPOINT AND CONFIGURATION LOG

Software Version
MBB
RCB
ECB
NAVI
SCB
CEM
MARQ
EXPANSION
Printed in U.S.A.
CESR131343--
CESR131249--
CESR131465-
CESR131227--
CESR131226--
CESR131174--
CESR131171--
RANGE
1 - 6 (multi-text strings)
0 - 1 (multi-text strings)
0 - 3 (multi-text strings)
Yes/No
0 - 60 min
0 - 60 min
Yes/No
0 - 2 (multi-text strings)
0 - 720 min
20 - 60
Yes/No
0 -1 (multi-text strings)
0 -1 (multi-text strings)
0 -1 (multi-text strings)
0 - 2 (multi-text strings)
Yes/No
0-100%
0 - 60000
0 - 900 sec
Yes/No
0 - 3
Enable/Disable
Enable/Disable
1 - 10
Enable/Disable
Enable/Disable
–10 - 10
–20 to 55 dF
0 - 600 sec
Yes/No
Yes/No
–20 - 20
10 - 120
0.0 - 5
0 - 5
0 - 50
Yes/No
25 - 100%
0 - 100%
15 - 60 sec
0 - 100%
15 - 60 sec
70 - 120 dF
70 - 120 dF
80 - 150 dF
Form 48/50A-13T
Pg CL-1
DEFAULT
ENTRY
4
1
0
No
0
0
No
0
50
20
No
0
1
0
1
No
20
0
0
No
0
Disable
Disable
5
Disable
Disable
1
40
60
No
No
–10
10
1
0.3
30
No
50
100
20
6
30
95
105
110
2-18
Replaces: 48/50A-12T