Economizer Options; Indoor Air Quality Options; Exhaust Options; Programming Operating Schedules - United Technologies Carrier Weathermaker 48A2 Controls, Start-Up, Operation, Service, And Troubleshooting

Single package large rooftop units with comfortlink version 8.x controls
Table of Contents

Advertisement

2. Install jumpers between R-W2 and W2-W1 on TB4 in
the control box.
3. Under the Setpoints menu, the following configurations
should be set:
OHSP
Occupied Heat Setpoint
OCSP
Occupied Cool Setpoint
UHSP
Unoccupied Heat Setpoint
UCSP
Unoccupied Cool Setpoint
GAP
Heat-Cool Setpoint Gap
SA.HI
Supply Air Setpoint Hi
SA.LO
Supply Air Setpoint Lo
4. The degrees of demand from the space temperature set-
points are configured under the Configuration
submenu. See the Heating Control and Cooling Control
sections for further description on these configurations.
Configure the following setpoints:
L.H.ON Demand Level Lo Heat On
H.H.ON Demand Level Hi Heat On
L.H.OF Demand Level Lo Heat On
L.C.ON Demand Level Lo Cool On
H.C.ON Demand Level Hi Cool On
L.C.OF
Demand Level Lo Cool On
5. Under Configuration
the space sensor by setting SPT.S to ENBL.
6. Under Configuration
for continuous fan or 0 for automatic fan.
7. To program time schedules, set SCH.N=1 under Config-
uration
CCN
SC.OV
control to use local schedules.
8. Under the Timeclock
sired schedule. See Time Clock Configuration section on
page 77 for further description of these configurations.
9. See the Economizer Options section below for additional
economizer option configurations.
10. See the Exhaust Options section on this page for
additional exhaust option configurations.
Economizer Options —
ECON submenu, the following setpoints may be configured:
EC.EN
Economizer Enabled?
EC.MN
Economizer Min.Position
EC.MX
Economizer Maximum Position
EP.MS
Economizer Position at Min. VFD
EP.XS
Economizer Position at Max. VFD
E.TRM
Economizer Trim for SumZ?
E.SEL
Econ Changeover Select
OA.E.C
OA Enthalpy Change Over Select
OA.EN
Outdoor Enthalpy Compare Value
OAT.L
High OAT Lockout Temp
O.DEW
OA Dew Point Temp Limit
ORH.S
Outside Air RH Sensor
Configuration
ECON
the minimum damper position. While practicing dual setpoint
usage, Cofiguration
ECON
to set up the dual minimum damper positions. The controller
would enforce EP.MS  EP.XS.
D.LV.T
UNIT
SENS
SPT.S, enable
UNIT
CV.FN, set CV.FN to 1
SCH.N to configure the
SCH.L submenu, enter the de-
Under the Configuration
EC.MN should always be set for
EP.MS and EP.XS are needed
Indoor Air Quality (IAQ) Options
DEMAND CONTROLLED VENTILATION — Under
Configuration
parameters should be set to establish the minimum and maxi-
mum points for outdoor air damper position during demand
controlled ventilation (DCV):
EC.MN
EP.MS
EP.XS
IAQ.M
Configuration
absolute minimum vent position (or maximum reset) under
DCV. Configuration
setup the dual minimum damper positions.
Configuration
minimum damper position (or with no DCV reset). This is also
referenced in the economizer section.
Exhaust Options —
ured with constant volume 2-stage power exhaust or modulat-
ing power exhaust. The following exhaust options should be
configured.
Configuration
— For two-stage exhaust, under the Configuration
menu, configure the following:
BP.P1
BP.P2
Configuration
Option) — For modulating exhaust, in the Configuration
BP submenu, configure the following:
BP.SP
Programming Operating Schedules —
The ComfortLink controls will accommodate up to eight dif-
ferent schedules (Periods 1 through 8), and each schedule is
assigned to the desired days of the week. Each schedule
includes an occupied on and off time. As an example, to set an
occupied schedule for 8 AM to 5 PM for Monday through Fri-
day, the user would set days Monday through Friday to ON for
Period 1. Then the user would configure the Period 1 Occupied
From point to 08:00 and the Period 1 Occupied To point to
17:00. To create a different weekend schedule, the user would
use Period 2 and set days Saturday and Sunday to ON with the
desired Occupied On and Off times. To create a schedule, per-
form the following procedure:
NOTE: By default, the time schedule periods are programmed
for 24 hours of occupied operation.
1. Scroll to the Configuration mode, and select CCN
CONFIGURATION (CCN). Scroll down to the Schedule
Number (Configuration
password protection has been enabled, the user will be
prompted to enter the password before any new data is
accepted. SCH.N has a range of 0 to 99. The default val-
ue is 1. A value of 0 is always occupied, and the unit will
control to its occupied setpoints. A value of 1 means the
unit will follow a local schedule, and a value of 65 to 99
means it will follow a CCN schedule. Schedules 2 to 64
are not used as the control only supports one internal/
local schedule. If one of the 2 to 64 schedules is config-
ured, then the control will force the number back to 1.
Make sure the value is set to 1 to use a local schedule.
2. Enter the Time Clock mode. Scroll down to the LOCAL
TIME SCHEDULE (SCH.L) sub-mode, and press
ENTER. Period 1 (PER.1) will be displayed. Press
ENTER to configure Period 1.
22
IAQ
DCV.C, the following configuration
Economizer Min. Position
Economizer Position at Min. VFD
Economizer Position at Max. VFD
IAQ Demand Vent Min. Pos.
IAQ
DCV.C
IAQ.M is used to set the
IAQ
EP.MS and EP.XS are needed to
IAQ
DCV.C
EC.MN is used to set the
The A Series units can be config-
BP
BF.CF=1 (Two-Stage Exhaust Option)
Power Exhaust On Setp. 1
Power Exhaust On Setp. 2
BP
BF.CF=2 (Modulating Power Exhaust
Building Pressure Setp.
CCN
SC.OV
BP sub-
SCH.N). If