Combustion Air Options - Lochinvar Copper-Fin 2067 Installation & Service Manual

Hide thumbs Also See for Copper-Fin 2067:
Table of Contents

Advertisement

1
Determine unit location

Combustion Air Options

Under no circumstances should a mechanical
⚠ CAUTION
room ever be under a negative pressure.
Particular care should be taken when exhaust
fans, clothes dryers, compressors, air handling
units, etc., take away air from the inlet.
This unit has four combustion air options.
1. Outside Combustion Air, No Ducts
You can direct outside combustion air to this unit using either
one or two permanent openings (see FIG. 1-5).
One Opening
The opening must have a minimum free area of one square
inch per 3000 Btu input (7 cm
opening within 12'' (30 cm) of the top of the enclosure.
Figure 1-5_Outside combustion air single opening
14
per kW). You must locate this
2
Installation & Service Manual
Two Openings
The combustion air opening must have a minimum free area
of one square inch per 4000 Btu input (5.5cm² per kW). You
must locate this opening within 12'' (30cm) of the bottom of
the enclosure.
The ventilation air opening must have a minimum free area
of one square inch per 4000 Btu input (5.5cm² per kW). You
must locate this opening within 12'' (30cm) of the top of the
enclosure.
Figure 1-6_Outside combustion air, two openings
2. Outside Combustion Air, Using Ducts
You can direct outside combustion air to this unit using two air
ducts to deliver the air to the boiler room.
Each of the two openings must have a minimum free area of one
square inch per 2000 Btu input (11cm² per kW).
Figure 1-7_Outside combustion air, using ducts