Trouble shooting 23
OUTDOOR UNIT Error Method:
4-way valve error
Detective Actuators:
Outdoor Unit Inverter PCB Circuit
4-way valve
Forecast of Cause :
1. Connector connection failure
5. Inverter PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Check thermistor
Isn't it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor,
If defective, replace the thermistor
OK
OK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN30 from PCB and check the resistance value of coil.
Resistance value is about 1.4k
>>If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature,
and the location of the valve by the temperature difference.
>>If the value location is not proper, replace 4-way valve.
OK
OK
Check Point 4 : Replace Inverter PCB
If Check Point 1- 3 do not improve the symptom, replace Inverter PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When the indoor heat exchanger temperature is compared with
the indoor temperature, and either following condition is detected
continuously two times, the compressor stops.
Cooling or Dry operation
[Indoor heat exchanger temp.] - [Indoor temp.] < -10degC
Heating operation
[Indoor heat exchanger temp.] - [Indoor temp.] > +10degC
the compressor stops permanently.
2. Thermistor failure
3. Coil failure
02-26
4. 4-way valve failure