Advantech LEO-S552-THG0 User Manual page 22

Temperature/humidity sensor
Table of Contents

Advertisement

4e (Pulse counter)
Example:
1. Set reporting interval as 20 minutes.
Channel
ff
2. Reboot the device.
Channel
ff
3. Set a temperature threshold as below 15°C or above 30°C.
Channel
06 (Set Threshold
ff
Alarm)
www.advantech.com
ff03b004
Type
03 (Set Reporting
Interval)
ff10ff
Type
10 (Reboot)
ff 06 cc96002c0100000000
Type
Number(1B)+Function(1B)+D2D
Command(2B)
Number:
01 -Temperature threshold trigger
02 -Temperature threshold doesn't
trigger
03 - Status trigger
04 -Status doesn't trigger
Function:
00 -Only use LoRaWAN
01 -Only use D2D
03 -Use D2D&LoRaWAN Uplink
0100-Clean the count
0101-Stop counting
0102-Start counting
Value
b0 04 => 04 b0 = 1200s
= 20 minutes
Value
ff (Reserved)
Value
CTRL:cc =>11001100
100 = below or above
Min:96 00=> 00 96 = 15°C