Downlink Commands - Advantech LEO-S552-THG0 User Manual

Temperature/humidity sensor
Table of Contents

Advertisement

Battery level is reported every 6 hours.
Channel
01
75(Battery Level)
03
67 (Temperature)
04
68(Humidity)
Examples:
LEO-S552-THG0
Channel
Type
75
01
(Battery)

5.3 Downlink Commands

LEO-S552-THG0 sensors support downlink commands to configure the device. The
application port is 85 by default.
Channe
l
03 (Set Reporting Interval)
06(Set Threshold Alarm)
ff
79(Set D2D settings)
www.advantech.com
Type
UINT8, Unit: %
INT16, Unit: °C, Resolution: 0.1 °C
INT8, Unit: %, Resolution: 0.5 %
01 75 64 03 67 10 01 04 68 71 05 00 01
Value
Channel
64 => 100%
03
Type
10 (Reboot)
Description
Type
67
10 01 => 01 10 = 272
(Temperature)
Temp=272*0.1=27.2°C
Description
2 Bytes, unit: s
9 Bytes, CTRL (1B) + Min (2B) +
Max (2B) +00000000(4B)
CTRL:
Bit0~Bit2:
000 - disable
001 - below (minimum threshold)
010 - above (maximum threshold)
011 - within
100 - below or above
Bit3~Bit7: 11001
ff(Reserved)
4 Bytes,
Value
21
2 1

Advertisement