General Information; Introduction; Specification Notes - Cornelius CH1500-CH7500 Operator's & Installation Manual

Cornelius chiller operator's manual with installation, service, and parts
Table of Contents

Advertisement

I
NTRODUCTION
Remcor "CH" Series Refrigerated Recirculating Water Chillers are designed to provide a continuous flow of clean
cooling water at a constant temperature and to handle a variety of closed loop and tank cooling applications.
The CH consists of a refrigeration system with associated operating controls housed in a sturdy sheet metal cabinet.
A standard pump and reservoir package provides a complete self-contained water cooling and circulating system.
CH Chillers are designed to operate in a clean laboratory or industrial environment where ambient temperatures
o
o
range from 40
F (4.4
C) to 110
free and provide a constant supply of cooling liquid to the application.
NOTE: Please read through this manual before starting the chiller.
Model
Cooling Capacity* Watts/BTU
Compressor
Condenser
Temperature Controller
Pump**
Reservoir
Voltage (Full Load Amps)
Dimensions W x D x H (inches)
Inlet/Outlet Fitting Size
S
N
PECIFICATION
1. The figures for power and cooling capacity are listed for air-cooled units with a circulation temperature of
o
68
F, and ambient temperature of 80
2. Cooling capacity will be affected as follows: Derate 17% for 50 Hz operation. Derate 1% for each degree
Fahrenheit drop in recirculating temperature. Derate .5% for each degree Fahrenheit increase in ambient
temperature. Optional pumps will decrease net cooling capacity.
3. The operating water temperature range for water is 40
or temperatures are required, the Technical Service Department must be contacted so the appropriate
ranges can be set.
4. Water-cooled units require about 20% less input power.
5. All CH Chillers are thoroughly tested before leaving the factory to ensure that each unit meets these spec-
ifications prior to shipment.
!
WARNING:
Never operate the chiller with the panels removed. Always use the power switch to turn off the chiller when it is not
being used. Always ensure that all air inlets and outlets are free of obstructions.
© 2006-2011, IMI Cornelius Inc.

GENERAL INFORMATION

o
o
F (43.3
C). Once properly installed, the CH Chiller will run virtually maintenance
Table 1. Specifications
OTES
o
F and standard pump.
CH5000 & CH7500 Chiller Operator's & Installation Manual
CH5000
17,584/60,000
5 H.P.
Air Cooled
Digital Display 40-100
2CS (12 GPM @ 50 PSI)
40 Gallons
CH5002A 230/60/3 (28)
CH5003A 460/60/3 (14)
36" x 36" x 65" (91.4cm x 91.4cm x 165cm)
o
o
F (4.4
C) to 100
- 3 -
CH7500
26,376/90,000
7.5 H.P.
o
o
F (4.4-37.8
C.)
CH7502A 230/60/3 (36)
CH7503A 460/60/3 (18)
1 inch
o
o
F (37.8
C). If use of other fluids
Publication Number: 91961OPR