Appendix A Blower Performance Tables - Amana APG16 M Series Installation Instructions Manual

Single package gas-electric heating & cooling unit
Table of Contents

Advertisement

APPENDIX A BLOWER PERFORMANCE TABLES

Burners High Fire Input: 140,000 BTU/HR
Down Flow
External
Speed
Static
Tap
Pressure
(ESP), in w.c.
0.2
0.4
T1
0.6
0.8
0.2
0.4
T2
0.6
0.8
0.2
0.4
T3
0.6
0.8
0.2
0.4
T4
0.6
0.8
0.2
0.4
T5
0.6
0.8
Shaded area indicates air flow below 1500 SCFM (300 SCFM/ton) that
is not recommended for High Stage cooling or heating
Models: APG1660140M41
Standard Static Drive
SCFM
RPM
BHP
983
570
0.14
833
659
0.16
703
739
0.18
574
808
0.19
1299 669
0.25
1193 730
0.27
1058 815
0.30
950
875
0.32
1770 825
0.53
1684 875
0.57
1595 926
0.60
1513 975
0.63
1862 859
0.62
1787 909
0.66
1702 955
0.69
1625 1005 0.73
2132 954
0.91
2056 993
0.95
1080 1038 0.99
1899 1079 1.03
5 Ton
Horizontal Flow
External
Speed
Tap
Pressure
(ESP), in w.c.
T1
T2
T3
T4
T5
25
Static
SCFM
0.2
1003 606
0.4
850
0.6
718
0.8
586
0.2
1325 710
0.4
1217 775
0.6
1080 866
0.8
969
0.2
1806 876
0.4
1718 930
0.6
1627 984
0.8
1544 1036 0.67
0.2
1901 912
0.4
1824 966
0.6
1737 1014 0.73
0.8
1658 1067 0.77
0.2
2175 1014 0.97
0.4
2098 1055 1.00
0.6
1102 1102 1.05
0.8
1938 1146 1.09
RPM
BHP
0.14
701
0.17
785
0.19
858
0.20
0.26
0.29
0.32
930
0.35
0.57
0.60
0.64
0.66
0.70

Advertisement

Table of Contents
loading

This manual is also suitable for:

Apg16mApg1660140m41