BBV, SBV Series Natural Vent Gas Fireplaces
1. Check gas type. The gas supply must be the same as
stated on the appliance's rating decal. If the gas sup-
ply is different from the fireplace, STOP! Do not install
the appliance. Contact your dealer immediately.
2. To ease installation, a 30" (762 mm) flex line with
manual shut-off valve has been provided with this ap-
pliance. Install and attach 1/2" gas line onto shut-off
valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to
the fireplace for leaks. Use a solution of 50/50 water
and soap or a gas sniffer.
4. To adjust flame height, turn HI/LO knob to HI to get
maximum pressure to burner. Turn HI/LO knob to LO
to get minimum pressure.
5. To check gas pressures at valve, turn captured screw
counterclockwise 2 or 3 turns and then place tubing
to pressure gauge over test point. Turn unit to high.
Figure 17. After taking pressure reading, be sure and
turn captured screw clockwise firmly to reseal. Do not
over torque. Check test points for gas leaks.

ELECTRICAL WIRING

Electrical connections should only be per-
formed by a qualified, licensed electrician.
Main power must be off when connecting to
main electrical power supply or performing
service. All wiring shall be in compliance
with all local, city and state codes. The ap-
pliance, when installed, just be electrically
grounded in accordance with local codes,
or in the absence of local codes, with the
National Electrical Code ANSI/NFPA 70 (lat-
est edition) and Canadian Electrical Code,
CSA C22.1.
16
CHECK GAS PRESSURE & ELECTRICAL INSTALLATION - MILLIVOLT
Pressure
Test "IN"
Pressure
Test "OUT"
HI/LO Knob
Pilot Adjustment Screw
Figure 17 -
Gas Pressure Check at Gas Valve
Do not use open flame to check for gas
leaks.
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.
Verify proper operation after servicing.
FP1979
62D4037