Con Guration - LEGRAND 574046 Quick Start Manual

Pir flush-mounted scs green switch

Advertisement

Con guration

1. Lighting Management System
When installed in a Lighting Management system, the device can be con gured in the
following ways:
- Plug & Go: automatic procedure for pairing devices connected to the inputs and outputs.
The procedure is activated on powering the device. It is only available for Room Control-
lers or, in the case of other devices, paired with the Room Controllers.
2. My Home system
If the device is installed in a My Home system it can be con gured in two ways:
- PHYSICAL CONFIGURATION, inserting the con gurators in position.
- Con guration via MYHOME_Suite software package, downloadable from
www.homesystems-legrandgroup.com; this mode has the advantage of o ering many
more options than the physical con guration.
3. Physical con guration
The sensor parameters are de ned by 6 con gurator sockets and the functions depend on the operating mode:
Local: A = 1 – 9
Light point: PL = 1 – 9
Mode: M = 0 – 4
Available functions
The sensor controls the light unit, the address of which de ned in A and PL. When a movement is detected, and if the measured brightness is below
the con gured value, the system switches on the speci ed light unit and keeps it on until the expiry of the period con gured using the con gurator on
T (automatic mode). The Sensitivity of the PIR movement detector is con gured using the con gurator on S. For appropriate operation, the sensitivity
of the light sensor must be con gured using the con gurator on D. If a user manually switches o the lights, a control action can be used to disable the
movement detector until a movement is detected, for a period set by T.
In this mode, the sensor only works based on the light conditions, and the movement sensor is disabled. When the brightness falls below the threshold
con gured, the system switches on the light unit, switching it o again when the brightness exceeds the set threshold (automatic mode). Con gure A =
1 -9 and PL = 1 - 9, con gurators GEN, AMB and GR cannot be connected. In this mode, con gurators S and T are not connected.
In this mode the sensor does not manage the lights directly, but sends movement and brightness signals to the scenario programmer MH200N. In this
case, the sensor address is entered in A and PL and must be unique inside the system. Therefore it is not possible to connect con gurators GEN, AMB, and
GR. In this mode the S and T con gurators are not connected because these parameters are directly managed by the scenario programmer.
In this mode the system directly manages a light unit, ensuring a consistent brightness level inside the room (this mode is only e ective if the sensor
manages the dimmer). The system switches the lights on when a movement is detected and keeps them on based on the presence of people and the
lighting threshold con gured (automatic mode). When a movement is detected, and if the measured brightness is below the con gured threshold, the
sensor switches the speci ed light unit on and keeps it on until the expiry of the period con gured using the con gurator on T. During operation, the
sensor keeps a constant brightness level, depending on the con gurator on D. For example, when the brightness of the natural light increases, the sensor
reduces the brightness of the light unit controlled. For appropriate operation, the brightness sensitivity threshold of the sensor must be con gured using
the D con gurator. The threshold value can be modi ed using a brightness control. The new value is then con gured as the new sensor threshold, until
the next activation
In this mode, the sensor only operates on the basis of the brightness conditions, and directly manages a light unit to ensure a constant brightness level
inside the room (this mode is only e ective if the sensor manages the dimmer). The movement sensor is disabled. The lights are manually switched on,
and automatically switched o by the sensor, based on the con gured brightness threshold (eco mode). Therefore, when the lights are o , the sensor
does not switch them on; but it waits for the user to switch them on manually. During operation, the sensor keeps a constant brightness level, depending
on the con gurator on D. For example, when the brightness of the natural light increases, the sensor reduces the brightness of the light unit controlled.
When the lights are o , if the level of natural light decreases, the sensor does not switch them on, but it waits for the user to switch them on manually.
For appropriate operation, the brightness sensitivity threshold of the sensor must be con gured using the D con gurator. The threshold value can be
modi ed using a brightness control. The new value is then con gured as the new sensor threshold, until the next activation.
Warning: To manage scenarios using the sensor signals, via the MH200N scenario programmer, the sensor must be con gured in Mode 2.
574046
067225
574096
AM5659
- Push & Learn: procedure for pairing di erent connected devices or changing the assign-
ments de ned automatically in the Plug & Go procedure. For more details, please refer
to the speci c document.
- Software Con guration: using the Virtual Con gurator software; for more details, please
refer to the speci c manual.
For a list of the procedures and their meanings, please refer to the instructions in
this sheet and to the "Function Descriptions" help section in the
MYHOME_Suite software package.
Sensitivity of the PIR movement sensor: S = 0 – 3
Control timer: T = 0 – 9
Sensitivity of the lights sensor: D = 0 – 5
Warning: the addresses A = 0 and PL = 0 do not exist
L/N/NT4659N
HD/HC/HS4659
Con gurator mode
0
1
2
3
4

Advertisement

loading