the power cables. If you want to change the power cables, please contact Gree's
local service center.
⑩. Wiring terminals should be connected firmly to the terminal board. Loose
connection is forbidden.
⑪. After the electrical installation is finished, please use wire clamps to secure the
power cords and the thermostat wires. Make sure the wires are not clamped too
tight.
⑫. The wire gauge of power cord should be large enough. Damaged power cords or
other wires must be replaced by specialized wires. Wiring work must be done
according to national wiring rules and regulations.
4.6.2 Electrical Parameters
Model
FLEXE24HP230V1AH
FLEXE30HP230V1AH
FLEXE36HP230V1AH
FLEXE42HP230V1AH
FLEXE48HP230V1AH
FLEXE60HP230V1AH
①. Fuse is located on the main board.
②. Install a circuit breaker at every power terminal near the units (indoor unit and
thermostat) with at least 3mm contact gap. The units must be able to be plugged
or unplugged.
③. Circuit breaker and power cord specifications listed in the above table are
determined based on the maximum power input of the units.
④. Specifications of circuit breaker are based on a working condition where the
working temperature is 40°C. If working condition changes, please adjust the
specifications according to national standards.
⑤. Adopt 5pc of AWG18 power cords to be the communication cords between indoor
unit and thermostat. The maximum length is 30m. Please select a proper length
according to local conditions. Communication cords must not be twisted together.
Power supply
208/230V-1Ph-60Hz
19
Minimum
circuit
ampacity (A)
protection (A)
1.8
3.2
4
4.3
6.9
7.5
Air Handlers
Maximum
overcurrent
15