Table of Contents

Advertisement

GAS PIPING
A properly sized gas supply system is essential for
maximum oven performance. Piping should be
sized to provide a supply of gas sufficient to meet
the maximum demand of all appliances on the line
without loss of pressure at the equipment.
Example:
NOTE: BTU values in the following example are
for natural gas.
You purchase a DFG-100 convection oven to add
to your existing cook line.
1. Add the BTU rating of your current appliances.
Pitco Fryer
6 Burner Range
Deck Oven
Total
2. Add the BTU rating of the new oven to the to-
tal.
Previous Total
DFG-100
New Total
3. Measure the distance from the gas meter to
the cook line. This is the pipe length. Let's say
the pipe length is 40' (12.2 m) and the pipe
size is 1" (2.54 cm).
4. Use the appropriate table to determine the to-
tal capacity of your current gas piping.
The total capacity for this example is 320,000
BTU. Since the total required gas pressure,
285,000 BTU is less than 320,000 BTU, the
current gas piping will not have to be in-
creased.
NOTE: The BTU capacities given in the tables are
for straight pipe lengths only. Any elbows
or other fittings will decrease pipe capaci-
ties. Contact your local gas supplier if you
have any questions.
Maximum Capacity of Iron Pipe in Cubic Feet
Length (ft)
L
120,000 BTU
60,000 BTU
50,000 BTU
230,000 BTU
230,000 BTU
Maximum Capacity of Pipe in Thousands of
55,000 BTU
BTU/hr of Undiluted L.P . Gas at 11" W.C.
285,000 BTU
Pipe Length
p
From the National Fuel Gas Code Part 10 Table 10-15
11
Installation
of Natural Gas Per Hour
(Pressure drop of 0.5 Inch W.C.)
Nominal Size, Inches
Pipe
p
h (f )
3/4"
1"
10
360
680
20
250
465
30
200
375
40
170
320
50
151
285
60
138
260
70
125
240
80
118
220
90
110
205
100
103
195
From the National Fuel Gas Code Part 10 Table 10-2
(Pressure drop of 0.5 Inch W.C.)
g
Outside Diameter, Inches
(ft)
(f )
3/4"
10
608
20
418
30
336
40
287
50
255
60
231
70
215
80
198
90
187
100
175

Gas Connection

1-1/4" 1-1/2"
2"
1400
2100 3950
950
1460 2750
770
1180 2200
660
990
1900
580
900
1680
530
810
1520
490
750
1400
460
690
1300
430
650
1220
400
620
1150
1"
1-1/2"
1146
3525
788
2423
632
1946
541
1665
480
1476
435
1337
404
1241
372
1144
351
1079
330
1014

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dfg-100 series

Table of Contents