Identifying Label; Outdoor Sensor Graph; Setting Outdoor Sensor Curve - Potterton 36 Installation And Service Manual

High efficiency wall hung condensing gas boiler
Table of Contents

Advertisement

Fig.38
Graph showing available curves
Fig.39
Control knob and setting curve
00
90
80
70
6.4.3
6.4.4
90 80 70
85°
80°
75°
70°
65°
60°
55°
50°
45°
40°
35°
30°
20°
15°
10°
There are 9 available curves. It is essential that expected outdoor temper­
atures and the user requirements are considered before selecting the
curve.
Boiler flow temperature is shown on the vertical axis. The outside tempera­
ture is along the horizontal axis.
6.4.5
10
20
30
40
50
60
PN-0000628

Identifying label

Important
The identifying label (7221476-01) supplied with the outdoor sen­
sor must be signed and affixed on or adjacent to the boiler. The
label must be readily accessible without removing the boiler cas­
ing or any other disassembly. This label is required to enable SAP
and energy assessors to identify that a weather compensation de­
vice is installed and connected .

Outdoor sensor graph

60
50
40
-5°

Setting outdoor sensor curve

1. Ensure that there is power to the boiler (though it is not necessary
for there to be any heating demand).
2. The central heating control knob should be turned clockwise to the
position which corresponds with the desired curve as shown on the
graph.
3. Curve 50 is recommended as the most suitable for the normal range
of conditions expected in the UK. Consider the type of dwelling and
discuss with the user their requirements — one of the other curves
may be more appropriate.
4. Normally the display will show the current temperature of the water
in the boiler. As the knob is turned the display will show the selected
curve.
5. Once the curve is set the installation and commissioning of the boil­
er can be completed.
Note
Explain to the user how to select a different temperature curve
and how the outdoor sensor regulates the boiler flow temperature.
Important
When an OpenTherm controller is connected adjustment of the
boiler, e.g. heating temperature, is made using the OpenTherm
controller rather than the boiler controls. The boiler controls are
overridden by the OpenTherm control. Please check the function­
ality with the manufacturer of the OpenTherm controller.
30
20
10
00
-10°
-15°
-20°
6 Installation
PN-0000627
45