Download Print this page

Mounting Procedures - Wheelock ET80-24MCW-FW Installation Instructions Manual

Advertisement

IMPROPER ELECTRICAL INPUT CAN DAMAGE THE PRODUCT OR CAUSE IT TO MALFUNCTION, WHICH COULD RESULT
IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

MOUNTING PROCEDURES:

CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and
conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used.
1.
ET80-24MCW model has an integrated Speaker Mounting Plate.
2.
The Speaker Mounting Plate must be oriented correctly when it is mounted to the backbox. Turn the Speaker Mounting Plate so
that the arrow above the words "Horizontal Strobe" points to the top side of the Speaker Mounting Plate.
3.
First mount the Speaker Mounting Plate to the backbox. Next slide the grille over the Speaker Mounting Plate strobe and attach
with (2) screws. Tamper-resistant Pan Torx screws have been provided.
4.
When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring
space for the signaling appliance.
5.
To move selector switch, insert screwdriver into slot shown on the bottom side of the strobe. The setting is indicated by a
pointer and can be seen on the bottom side of the lens. See Figure 5.
6.
Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.
7.
Do not pass additional wires (used for other than the signaling appliance) through the backbox. Such additional wires could
result in insufficient wiring space for the signaling appliance.
8.
Mounting hardware for each mounting option is supplied.
9.
The ET80-24MCW can be flush mounted to a 4" square by 2-1/8" deep backbox with a 4" square 1-1/2" extension ring (Figure
A) or surface mounted to a Surface Backbox (Figure B).
10. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum
stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
INSERT
SCREWDRIVER
WARNING:
THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA
INTENSITY BEFORE INSTALLATION. WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH,
MAKE CERTAIN THAT IT "CLICKS" IN PLACE. AFTER CHANGING THE CANDELA SETTING, THE APPLIANCE
MUST BE RETESTED TO VERIFY PROPER OPERATION. IMPROPER SETTING OF THE CANDELA SELECT
SWITCH, MAY RESULT IN OPERATION AT THE WRONG CANDELA, WHICH COULD RESULT IN PROPERTY
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
Figure 5:
15
75
NOTE: The ET80-24MCW comes pre-set at 15cd.
30
1
1
0
CANDELA
POINTER
P84506 B
Sheet 5 of 8