Setup Of The Powermaxx - Delta PowerMaxx DMS-280 Installation & Operating Instructions Manual

Pump station battery backup
Table of Contents

Advertisement

PowerMaxx
9.0

Setup of the PowerMaxx

1.
Ensure that the mains power is off.
2.
Replace the fuses to the spurs supplying the PowerMaxx and turn on the mains power.
3.
Check that the pump/s are receiving power (with the PowerMaxx switched off) by lifting the float
switches on the pump/s.
4.
Switch the PowerMaxx on, all three LEDs should flash three times.
5.
The blue LED will be permanently lit while the PowerMaxx checks the environment and the connections.
6.
After 10-20 seconds one of the following LED combinations will be displayed.
Red
Blue
LED
LED
4/sec
On
3/sec
On
2/sec
On
1/sec
On
On
On
7.
If the PowerMaxx fails to configure correctly - switch the unit off, remove the fuses from the spurs and
redo the connections or set the configuration switches to the correct positions (section 8.0) and turn the
unit back on. If the issue still persists please call technical support on 01279 757400.
8.
If you are connecting an AlertMaxx, please refer to the MaxxConnect installation & operating
instructions before proceeding further.
9.
Replace the covers of the PowerMaxx.
10. The PowerMaxx will always begin charging after it has been connected and configured. It may take
up to 15 hours (depending on the state of the battery) to fully charge.
8
Green
LED
No battery connected
No primary mains present
Secondary mains present and switch 2 in 1 pump position
No secondary mains present. Note: this can only occur if you have
set the configuration switch to 2 pumps (switch 2: Up) and have no
secondary mains present
Error in connection of cabling (reversed of mains and pumps)
1/sec
The unit is correctly connected
2/sec
The unit is correctly connected and charging
PowerMaxx during initial configuration
For technical support, please call 01279 757400