Thank you for purchasing this Airflow Hi-flow pump. This manual gives instructions on the correct installation. It is important that you follow these instructions carefully. This Airflow Pump is designed to collect condensate water from Air Conditioning systems and discharge it up to a...
Page 3
Dimensions HI-FLOW 1L HI-FLOW 2L 99.4 mm 131 mm 132 mm 164 mm 244mm 198mm 244mm 148mm...
Page 4
• Pump rating: 230V AC, 0.6A • Max. water flow rate (h @ 0m/ft): 288L/76 US Gal • Max head: 5m/16.5ft • Tank Capacity: 1L/2L • Sound level @ 1m (at 50Hz): 60dB(A) • Rated: Continuously • Class: Class I appliance •...
Page 5
Operation of this pump is via the internal float which activates a micro switch. It also includes a Hi Level Safety Switch (operated by a second internal float) which can be used to stop the air conditioning system in the unlikely event of pump failure. IMPORTANT: This pump has been designed for the removal of PH neutral condensate water only.
Page 7
The pump is designed to sit level on its base or to be fixed to a vertical surface. A spirit level is built in to the pump’s casing to aid levelling the pump. x2 screw holes are provided in the back plate of the pump for fixture to a vertical surface.
Page 9
The pump must be earthed. It is suitable for connection to a 230v 50hz AC power supply using the Supply Cable provided. Connection to the electrical supply must be via a double pole isolation switch having a separation of at least 3mm in each pole (Brown Live, Blue = Neutral, Green/Yellow = Earth).
Page 10
The following diagrams indicate three methods in which the hi level safety switch can be used to interrupt the live connection between the fan coil and the condenser. Electrical installation must be carried out by a competent person and be in accordance with local wiring regulations.
Page 11
A. Live connection is < 3 amps B. Via a suitable contactor relay (normally open) where the live connection is above 3 amps C. Where interruption of the live or neutral connections lead to comms problems...
Page 12
If the supply cord is damaged the pump must be switched off until the supply cord is replaced by a suitably qualified person to avoid a hazard. Note: Servicing and maintenance should be carried out by a competent person. For further help please contact Airflow Developments.
Page 13
Outlet Pipe – Check pipe and outlet barb are not blocked with debris or kinked. Reservoir – Check reservoir is not blocked with debris. Note: Fault conditions should be checked by a competent person. If these checks do not resolve the problem please contact Airflow Developments for further assistance.