SETTING UP THE BURNER
After burner output has been determined, use TABLE below AS AN INITIAL GUIDE for burner settings.
All settings in this table were obtained under the following conditions.
0 (zero) draft in the combustion zone;
●
Inlet gas pressure range as in table;
●
Gas inlet
pressure range
"wc
12.0 - 14.0
Manifold
Diaphragm
gas pressure
Marking
"wc
A11
A12
A13
3.5
A14
A15
A16
Standard lab test boiler;
●
Steady state (HOT) operating conditions.
●
Burner
output
Btu/hr
38,000
45,501
60,708
68,180
95,265
120,000
17
GB
Head
Air gate
setting
setting
Nocth
Notch
0
0.6
0
1
0
1.5
1
1.7
2
2
3
2.8
2903332