Cooling Mode Dehumidification; On Demand Dehumidification Airflow Adjustment - Rheem RGEA16 Installation Instructions Manual

Table of Contents

Advertisement

TABLE 10
ODD TERMINAL
INDOOR
INPUT TO "ODD"
MBIENT
TERMIN L
CONDITION
(FROM HUMIDIST T)
HIGH HUMIDITY
Ø V C
LOW HUMIDITY
24 V C
H. COOLING MODE DEHUMIDIFIC TION
n Explanation of On Demand Dehumidification Use
"On-Demand Dehumidification" (ODD) is an optional feature of the ECM interface board. The
ODD allows the user to have automatic dehumidification in the cooling mode that is controlled
by the user's dehumidifying thermostat or humidistat setting. The humidistat should be wired
between the ODD (grey) pigtail and the R (red) pigtail. (Note: no field wiring should be con-
nected directly to the ECM interface board.) When the humidity exceeds the humidistat set-
ting, the airflow is decreased by a preprogrammed amount. This results in higher latent
capacity and increases the level of comfort.
Use of the ODD feature is important if maximum latent removal is desired. These systems
typically have a latent capacity between 24% to 28% of total system capacity. ODD drops
cooling airflow to boost latent capacity without significantly reducing total system capacity.
Refer to the thermostat wiring section of this manual for recommended dehumidifying ther-
mostats.
IMPORTANT: Typical dehumidistats apply a 24V signal when humidity is high. This board
requires 24V when humidity is low. (See Table 10.)
I. ON DEM ND DEHUMIDIFIC TION IRFLOW DJUSTMENT
Use switches 9 & 10 to lower cooling airflow as defined in the following table:
IMPORTANT: Selection A turns off the input of the ODD terminal. DO NOT USE SELECTION
A WITH A DEHUMIDIFYING THERMOSTAT OR HUMIDISTAT (refer to Figure 29).
FIGURE 29
9 10
9 10
O
O
O
N
N
N
A
B
SWITCH 9
SELECTION
POSITION
A
OFF
B
ON
C
OFF
D
ON
EXPL N TION OF BOVE SELECTIONS:
Selection A: Maximum Latent Removal
This selection lowers cooling airflow to maximize latent removal anytime there is a call for
cooling. This selection can be used in environments where there is always a high latent
load as in coastal and southern regions of the USA (see Table 11).
NOTE: Use of selection A in arid environments is not necessary and may cause unneces-
sary power consumption.
9 10
9 10
O
N
C
D
SWITCH 10
COOLING AIRFLOW ADJUSTMENT
POSITION
MAXIMUM LATENT REMOVAL
OFF
(WITHOUT ODD INPUT)
OFF
(FACTORY SETTING)
ON DEMAND DEHUMIDIFICATION
ON
ON
NONE
(WITH ODD INPUT)
NONE
39

Advertisement

Table of Contents
loading

Table of Contents